1MRK506375-UEN Rev. N
tDelayAlm4thHD: It defines the alarm time limit for the calculated fourth harmonic distortion which is
applied after the warning signal pickup and depends on its sustainability.
WrnLimit5thHD: It defines the warning limit for the calculated fifth harmonic distortion. According to
standard IEEE 519-2014, harmonic voltage distortions on power system 161 kV and above is limited
to 1.0% for each individual harmonic.
tDelayAlm5thHD: It defines the alarm time limit for the calculated fifth harmonic distortion which is
applied after the warning signal pickup and depends on its sustainability.
WrnLimit6thHD: It defines the warning limit for the calculated sixth harmonic distortion. According to
standard IEEE 519-2014, harmonic voltage distortions on power system 161 kV and above is limited
to 1.0% for each individual harmonic.
tDelayAlm6thHD: It defines the alarm time limit for the calculated sixth harmonic distortion which is
applied after the warning signal pickup and depends on its sustainability.
WrnLimit7thHD: It defines the warning limit for the calculated seventh harmonic distortion. According
to standard IEEE 519-2014, harmonic voltage distortions on power system 161 kV and above is
limited to 1.0% for each individual harmonic.
tDelayAlm7thHD: It defines the alarm time limit for the calculated seventh harmonic distortion which
is applied after the warning signal pickup and depends on its sustainability.
WrnLimit8thHD: It defines the warning limit for the calculated eighth harmonic distortion. According to
standard IEEE 519-2014, harmonic voltage distortions on power system 161 kV and above is limited
to 1.0% for each individual harmonic.
tDelayAlm8thHD: It defines the alarm time limit for the calculated eighth harmonic distortion which is
applied after the warning signal pickup and depends on its sustainability.
WrnLimit9thHD: It defines the warning limit for the calculated ninth harmonic distortion. According to
standard IEEE 519-2014, harmonic voltage distortions on power system 161 kV and above is limited
to 1.0% for each individual harmonic.
tDelayAlm9thHD: It defines the alarm time limit for the calculated ninth harmonic distortion which is
applied after the warning signal pickup and depends on its sustainability.
15.13
Fault current and voltage monitoring function
FLTMMXU
15.13.1
Function revision history
Document
revision
A
B
C
D
E
F
G
J
Table continues on next page
Railway application RER670
Application manual
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
-
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 15
Monitoring
GUID-B976D374-CB18-441E-9A12-D4B351D6BF7F v1
GUID-0AA99E78-0C76-48B5-AA00-8E3201C0D263 v2
347

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer670

Table of Contents