1MRK506375-UEN Rev. N
VPBC12TR (sect.2)
IEC04000485 V1 EN-US
Figure 101:
For a bus-coupler bay in section 2, the same conditions as above are valid by changing section 1 to
section 2 and vice versa.
12.4.3.5
Configuration setting
If there is no bypass busbar and therefore no QB2 and QB7 disconnectors, then the interlocking for
QB2 and QB7 is not used. The states for QB2, QB7, QC71 are set to open by setting the appropriate
module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
QB2_OP = 1
QB2_CL = 0
QB7_OP = 1
QB7_CL = 0
QC71_OP = 1
QC71_CL = 0
If there is no second busbar B and therefore no QB2 and QB20 disconnectors, then the interlocking
for QB2 and QB20 are not used. The states for QB2, QB20, QC21, BC_12, BBTR are set to open by
setting the appropriate module inputs as follows. In the functional block diagram, 0 and 1 are
designated 0=FALSE and 1=TRUE:
QB2_OP = 1
QB2_CL = 0
QB20_OP = 1
QB20_CL = 0
QC21_OP = 1
QC21_CL = 0
BC_12_CL = 0
VP_BC_12 = 1
BBTR_OP = 1
VP_BBTR = 1
12.4.4
Interlocking for transformer bay AB_TRAFO
Railway application RER670
Application manual
DCCLTR (A1A2)
DCCLTR (B1B2)
BC12CLTR (sect.2)
VPDCTR (A1A2)
VPDCTR (B1B2)
EXDU_DC (A1A2)
EXDU_DC (B1B2)
EXDU_BC (sect.2)
Signals to a bus-coupler bay in section 1 from a bus-coupler bay in another
section
© 2017 - 2023 Hitachi Energy. All rights reserved
BC_12_CL
&
VP_BC_12
&
EXDU_BC
&
en04000485.vsd
Section 12
Control
M13553-107 v4
IP14149-1 v2
245