Detection Zone - Honeywell Ex-Or BattenFit MSB1000T Installation And Commissioning Instructions

Sensor switching/switching with photocell

Advertisement

If the distance between the bottom
of the sensor and the bottom of the
end cap exceeds 59mm, there may
be a blind spot in the detection
zone.
Walk Testing
In order to verify the installation, there is an inbuilt facility (Walk Test Mode) to temporarily reduce the time delay
to 10 seconds. A QuickSet Pro or HP18 Programmer is required to access this facility.
Using the HP18:
Press the 'TEST' button to enable walk test mode.
Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before
moving and triggering the lights back on.
Re-programme the desired Off Delay once testing is complete (MSB1000PT only).
Using the QuickSet Pro:
Go to the Utilities menu, choose 'LightSpot/MLS/LCM' then 'User Test', place the cursor over 'Walk Test', point
the programmer at the detector and press OK.
Move around the area that is being controlled, stopping for 10 seconds to allow the lights to switch off, before
moving and triggering the lights back on.
After 5 minutes, the time-out will be restored to what it was before walk test was enabled.
Notes on Walk Testing:
During walk test, after the lights have turned off, wait 5 seconds before moving again because the sensitivity
l
is deliberately reduced for a few seconds following switch off.
Sensitivity is greater when approaching the circular footprint at a tangent rather than heading towards the
l
centre (see Fig. 7).
Most luminaires take approximately 1 second to strike after presence has been detected.
l
The detection pattern is cone-shaped which means that when standing at the very edge of the detection
l
footprint only a person's feet will be visible (see Fig. 8).

DETECTION ZONE

Fig. 9
- 5 -