Sensor switching/switching with photocell

Advertisement

BattenFit Sensor: MSB1000T - Switching
Only suitably qualified personnel should install this equipment.
This passive infrared presence detector is designed to be fitted to a batten-style luminaire.
Installation
1. Remove the M20 knockout from the end cap of the luminaire.
2. Pass the sensor wires through from the outside and insert the threaded end of the sensor into the hole.
3. A polarising plate can be made in order to prevent rotation of the sensor - an example design is given
below (Fig. 4).
4. If a polarising plate is to be used, pass the wires through the slot and position the polarising plate against
the inside face of the end cap. Ensure that the tab is positioned correctly i.e. at the ceiling side, away from
the lamp.
5. Fit and tighten the locknut.
6. Connect the wires in accordance with the wiring instructions.
Fig. 1
Polarising Plate (not supplied)
The purpose of the polarising plate is to ensure that the sensor does
not rotate from the correct position, i.e. pointing vertically
downwards, during transport or installation.
The two overall dimensions marked 'SEE TEXT' need to be made
such that when the plate is positioned against the inner face of the
luminaire end cap, it cannot rotate.
The 3.5mm 'tab' should be located closest to the ceiling (away from
the lamp). The 6.0mm slot is optional and is to allow the wires to
pass through for ease of assembly.
Material can be plastic sheet, minimum thicknesss 1.0mm,
recommended thickness 1.5-2.0mm, or mild/stainless steel sheet,
minimum thickness 0.6mm, recommended thickness 1.0-1.6mm.
MSB1000PT - Switching with photocell
Fig. 2
If there is insufficient space
for the locknut, the adaptor
shown below (Fig. 3) can be
used.
Fig. 3
- 2 -
20mm Female Adaptor
MK part number EFA/2
SEE TEXT
3.5
20
6.0
Fig. 4