Before You Begin Installing
WIDP-WGI Wireless Gateway
A
Total System Current
Auxiliary Devices
IPDACT-2 IP Communicator
IPDACT-2UD IP Communicator
CELL-MOD/CELL-CAB-SK
HWF2-COM Series
B
Auxiliary Devices Current
Notification Devices
5495/5499 Power Supply
C
Notification Appliances Current
D
Total current ratings of all devices in system (line A + line B + C)
E
Total current ratings converted to amperes (line D x 0.001):
F
Number of standby hours
G
Multiply lines E and F.
H
Alarm sounding period in hours. (For example, 5 minutes = 0.0833 hours)
I
Multiply lines E and H.
J
Add lines G and I.
1
The FACP can only support 5 devices with LEDs on. The current draw has been added to the panels alarm current.
2
The SK-BEAM-T draws a maximum of 500mA from auxiliary power when the test feature is used. This should be considered when
determining auxiliary power capacity but not calculated into current requirements for everyday operation.
3
Maximum SBUS address capacity is determined by the amount of SBUS bandwidth consumed by each SBUS module. Refer to the FACP
manual for SBUS limitations.
4
If there are door holders in the system, there is no need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the 1.8 A total current that
can be drawn from the panel.
5
Use next size battery with capacity greater than required.
2.5.4 Current Draw Worksheet for SD SLC Devices
For each RPS-1000 in the installation, use this worksheet in Table 2.6 to determine current requirements during alarm/battery standby oper-
ation. See individual FACP manual for maximum number of devices.
For each device use this formula:
RPS-1000 Intelligent Power
Module (Current draw from
battery)
20
Device
# of Devices
Refer to devices manual for current rating
4
Refer to device manual for current rating
Table 2.5 Current Draw Worksheet for SK SLC Devices
Device
# of Devices
This column
1*
Table 2.6 Current Draw Worksheet for SD SLC Devices
Current per Device
Max current using ext supply
Max current SLC Power
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
Standby:
Alarm:
Alarm/Standby:
Alarm/Standby:
Standby:
Alarm:
Alarm:
Alarm:
Alarm:
Total standby AH
Total alarm AH
Total ampere hours
5
required
Current per Device
X
This column
=
Standby
Alarm:
RPS-1000 Manual — P/N 151153:R 2/15/2022
Calculating Current Draw and Standby Battery
Standby
Current
40 mA
mA
24 mA
mA
93 mA
mA
136 mA
98 mA
mA
155 mA
55 mA
mA
100 mA
210 mA
mA
290 mA
mA
mA
mA
mA
75 mA
205 mA
mA
mA
mA
mA
A
H
AH
AH
Standby
Current
Current per number of devices.
40 mA
40 mA
160 mA
Alarm Current
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
A
H
AH
Alarm Current
160 mA

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt rps-1000

Table of Contents