Wiring Specifications
The total worst case current is calculated as follows:
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
RPS-1000 Manual — P/N 151153:R 2/15/2022
RA-1000 Current Draw
RPS-1000 Current Draw
5865 Current Draw
5824 Current Draw
Total Worst Case Current Draw
= 2 x 0.100 amps
= 0.200 amps
= 1 x 0.010 amps
= 0.010 amps
= 1 x 0.200 amps
= 0.200 amps
= 1 x 0.040 amps
= 0.040 amps
= 0.450 amps