Section 11
Testing functionality by secondary injection
PUDIFLx
IECEQUATION19376 V1 EN-US
Verifying the function in Ungrounded mode
The following procedures are performed to test the function in Ungrounded mode.
If there is a VT present in the neutral, then the setting NeutVoltMeas is set to available.
1.
Set the following parameters:
2.
Activate RESETCOMP input to ensure that the stored values are reset.
3.
The expected output is monitored in the following path from the local HMI client: Main menu /
Test/Function status /Unbalance protection/CapBankPhaseVoltageDiff(87V, Ud>)/
SCPDPTOV(87V, Ud>):x/Outputs , where x = instance number.
4.
check the respective operation of warning, alarm, and trip.
Step no.
4-a*
4-b
4-c
RESETCOMP Test
4-d
4-e
4-f * *
Table continues on next page
212
UDIFLx
=
´
100
UBase
3
Operation = ON
tDefWrn = 5 s; tDefAlm = 5 s; tDefTrip =5 s
SCBGndType = Ungrounded
NeutVoltMeas = Available
Udif> =10% UB
UdifAlm> =8% UB
UdifWrn> = 5% UB
UMin> =50% UB
VoltRatioL1 =0.5
Changes after step 2
Inject constant bus voltages of U
V at 0°, U
= 63.51 V at 240°, and U
L2
63.51 V at 120° in secondary at rated
Inject constant tap voltage of U
31.75 V in secondary at rated frequency
Inject constant neutral voltage of U
in secondary at rated frequency
Activate binary input RESETCOMP for 1 s
Inject U
TapL1
rated frequency
Activate binary input TRIGCOMP for 1 s
© 2017 - 2022 Hitachi Energy. All rights reserved
= 63.51
L1
=
L3
=
TapL1
= 1 V
N
TRIGCOMP Test
Repeat
Sub-step 4–a
= 31.75 V in secondary at
1MRK 504 165-UEN Rev. K
GUID-069FCF45-61B1-486C-8C0E-D1CC66B3BB3F v1
Expected output
UL1, UL2, and UL3 should show
230.94 kV
UTAPL1 should show 115.47 kV
UNSCB should show 36.63 kV
USEDURATL1 should show 0.5
(VoltRatioL1)
DIFURATL1 should become
HIGH
URATIOL1 and USEDURATL1
should show 0.492 and 0.5
respectively
The output COMPEXED
should become HIGH for 100
ms and LASTCOMP output
should display the date and
time of compensation
URATIOL1 and USEDURATL1
should show 0.406
DIFURATL1 should become
LOW
Transformer protection RET670
Commissioning manual
(Equation 111)