The ControlEdge HC900 is equipped with an Ethernet port as a standard feature (two Ethernet ports on
the C70
& C75 CPU). These ports can function simultaneously as slave and master communications ports.
The dual Ethernet ports (C70 & C75 CPU's) can be configured for redundant operation to a host.
If the host device does not have the inherent capability to recognize a network failover, the
Honeywell HWIOPC Server would be used to perform this functionality.
The dual Ethernet ports will not operate in a redundant configuration through a gateway to a
Host / server on another subnet. While both the E1 & E2 Ethernet can be configured with a default
Gateway address, only the E1 port will communicate across a gateway to another subnet.
2.4.

Hardware Components

This section contains general descriptions of each of the major components of the ControlEdge HC900
system.
For environmental specifications, refer to the section on Pre-Installation Planning.
ControlEdge HC900 Controller Rack
A ControlEdge HC900 Controller ("local rack") is shown in the following figure. As indicated in the
figure below, the Controller Rack includes:
1. Rack, available in 4- 8-, or 12-slot versions
2. Power Supply
3. Controller Module
4. Grounding bars (for I/O wiring; optional)
5. Input/Output modules.
6. I/O Terminal Blocks
Figure 7 – Controller Rack Components
Revision 10
ControlEdge HC900 Process & Safety Controller User and Installation Manual
21
May 2019