Mounting for Remote monitor

The E3Point Remote Monitor is designed to be mounted in an extra wide (2 3/8")
electrical box (not supplied) in the same way as a faceplate. Suggested electrical
boxes include T&B BC1110, Hubbell 1110, OZ-Gedney 18112, Appleton 18112,
Bowers 10612-BW, or Steel City 68371-12.
It does not fit on 4x4" steel boxes with a single gang mud ring, such as T&B 52CO
or 52C13.
● Run the wires through the electrical box and connect to the remote monitor.
● Press the monitor (2) into the faceplate (1) and close and press the back cover (3) into
the faceplate. You should hear a click.
Securely mount the monitor to the extra wide electrical box (4) using the
appropriate screws (5)(not supplied).
General Mounting Considerations:
Must be easily accessible for calibration and maintenance.
Mount the sensor close to the potential leak source for fastest possible
leak detection.
If personnel protection is the primary application, mount in the "breathing
zone" (3.3–5 ft/1–1.5 m from the ground, within the range of a person's
respiration area).
Take air movement and ventilation patterns into account.
See Warnings and Cautions on page 2 for additional considerations.
!