Honeywell 7800 Series Installation Instruction page 5

Relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

Ground Type
Earth ground (subbase and relay module).
Signal ground (KDM, Data ControlBus Module™,
Communications Interface ControlBus™ Module).
Terminal No.
G
Flame Sensor Ground
Earth G
Earth Ground
L2(N)
Line Voltage Common
3
Alarm
4
Line Voltage Supply (L1)
5
Burner Motor
6
Burner Controller and Limits
7
Lockout/Running Interlock
8
Pilot Valve/Ignition
9
Main Fuel Valve
10
Ignition
F(11)
Flame Sensor
12
Firing Rate High Fire
13
Firing Rate Common
14
Firing Rate Low Fire
15
Firing Rate Modulate
16
Unused
17
Unused
18
Low Fire Switch Input
19
High Fire Switch Input
20
Preignition Interlock Input
21
Interrupted/Intermittent Pilot Valve/First Stage Oil Valve
22
Shutter
a
.
The relay module must have an earth ground providing a connection between the subbase and the control panel or the
equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in event of an
internal short circuit. The relay module requires a low impedance ground connection to the equipment frame, which, in turn,
requires a low impedance connection to earth ground.
b
2000 VA maximum connected load to relay module assembly.
c
See tables 4 and 5.
d
RM7800G,M/RM7840G,M operating frequency determined by relay module selection.
บริ ษ ั ท เอดี ด ี เฟอร์ เ นส จํ า กั ด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258
https://www.add-furnace.com E-mail: sales@add-furnace.com
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES
Table 2. Recommended Grounding Practices.
Use the shield of the signal wire to ground the device to the
signal ground terminals [3(c)] of each device. Connect the
shield at both ends of the chain to earth ground.
Table 3. Terminal Ratings.
Description
a
a
5
Recommended Practice
1. Use to provide a connection between the subbase and
the control panel of the equipment. Earth ground must be
capable of conducting enough current to blow the 20A fuse
(or breaker) in the event of an internal short circuit.
2. Use wide straps or brackets to provide minimum length,
maximum surface area ground conductors. If a leadwire
must be used, use 14 AWG copper wire.
3. Make sure that mechanically tightened joints along the
ground path are free of nonconductive coatings and pro-
tected against corrosion on mating surfaces.
120 Vac, 1A pilot duty.
120 Vac (+10%/-15%), 50 or 60 Hz (± 10%)
120 Vac, 9.8 AFL, 58.8 ALR (inrush).
120 Vac, 1 mA.
120 Vac, 8A run, 43A inrush.
c
120 Vac
.
c
120 Vac
.
c
120 Vac
.
60 to 220 Vac, current limited.
120 Vac, 75 VA pilot duty.
120 Vac, 75 VA pilot duty.
120 Vac, 75 VA pilot duty.
120 Vac, 75 VA pilot duty.
120 Vac, 1 mA.
120 Vac, 1 mA.
120 Vac, 1 mA.
c
120 Vac
.
120 Vac, 0.5A.
Ratings
b,d
66-1085—3