Honeywell 7800 Series Installation Instruction page 15

Relay modules
Hide thumbs Also See for 7800 Series:
Table of Contents

Advertisement

RM7800I
Test
RM7840
Test
No.
Models
Jumpers Voltmeter
1
All
None
2
3
4
4-5
5
4-10
6
All
4-8
7
4-21
8
4-9
9
4-3
10
RM7800E,G,L;
4-5
RM7840E,G,L
and
12-13
4-5
11
RM7800E,G,L;
RM7840E,G,L
and
14-13
12
RM7800E,L;
4-5
RM7840E,L
and
12-13
13
RM7800E,L;
4-5
RM7840E,L
and
14-13
14
RM7800E,G,L;
15-13
RM7840E,G,L
บริ ษ ั ท เอดี ด ี เฟอร์ เ นส จํ า กั ด
ADD FURNACE CO.,LTD.
44 ซอยบรมราชชนนี 70 ถนนบรมราชชนนี แขวงศาลาธรรมสพน์ เขตทวี ว ั ฒ นา กรุ ง เทพฯ 10170
โทร: 02-888-3472 โทร: ออกแบบ:08-08-170-170 แฟกซ์ : 02-888-3258
https://www.add-furnace.com E-mail: sales@add-furnace.com
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES
Table 8. Static Checkout.
Normal Operation
4-L2
Line voltage at Terminal 4.
6-L2
Line voltage at Terminal 6.
20-L2
Line voltage at Terminal 20.
7-L2
1. Burner motor (fan or
blower) starts.
2. Line voltage at Terminal
7 within 10 seconds.
Ignition spark (if ignition
transformer is connected to
Terminal 10)
1. Ignition spark (if ignition
transformer is connected to
Terminal 8).
2. Automatic pilot valve opens (if
connected to Terminal 8).
NOTE: Refer to wiring diagram of
system being tested.
Same as test no. 6 for connections
to Terminal 8. If using direct spark
ignition, check the first stage fuel
valve(s) instead of the pilot valve.
Automatic main fuel valve(s) open.
If using direct spark ignition on a
model with intermittent pilot on
Terminal 21, check the optional
second stage fuel valve, if used.
Alarm (if used) turns on.
18-L2
Firing rate motor drives open; zero
volts at Terminal 18 after motor
starts driving open.
18-L2
Firing rate motor drives closed; line
voltage at Terminal 18 after motor
is in Low Fire position.
19-L2
Firing rate motor drives open; line
voltage at Terminal 19 after motor
is in High Fire position.
19-L2
Firing rate motor drives closed;
zero volts at Terminal 19 after
motor starts driving closed.
1. Raise setpoint of Series 90
controller—firing rate motor
should drive toward open.
2. Lower setpoint of Series 90
controller—firing rate motor
should drive toward closed.
15
If Operation is Abnormal,
Check the Items Listed Below
1. Master Switch.
2. Power connected to the Master Switch.
3. Overload protection (fuse, circuit breaker,
etc.) has not opened the power line.
1. Limits.
2. Burner Controller.
1. Preignition interlocks.
1. Burner motor circuit.
a. Manual switch of burner motor.
b. Burner motor power supply, overload
protection, and starter.
c. Burner motor.
2. Running or Lockout Interlocks (including
Airflow Switch).
1. Watch for spark or listen for buzz.
a. Ignition electrodes are clean.
b. Ignition transformer is okay.
1. Watch for spark or listen for buzz.
a. Ignition electrodes are clean.
b. Ignition transformer is okay.
2. Listen for click or feel head of valve for
activation.
a. Actuator if used.
b. Pilot valve.
Same as test no. 6. If using direct spark
ignition, check the first stage fuel valve(s)
instead of the pilot valve.
1. Listen for and observe operation of the
main
fuel valve(s) and actuator(s).
2. Valve(s) and actuator(s).
1. Alarm.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
1. High Fire Purge Switch.
2. Firing rate motor and transformer.
1. Low Fire Start Switch.
2. Firing rate motor and transformer.
1. Series 90 Controller.
2. Firing rate motor and transformer.
66-1085—3