Func.
N a m e
Code
d005
Intelligent input
terminal status
Intelligent output
d006
terminal status
d007
Scaled output frequency
monitor
d008
Actual frequency monitor
Torque command monitor
d009
d010
Torque bias monitor
d012
Output torque monitor
Output voltage monitor
d013
d014
Input power monitor
Watt-hour monitor
d015
Elapsed RUN time monitor
d016
Elapsed power-on time
d017
monitor
Heat sink temperature monitor
d018
d022
Life check monitor
" d " F u n c t i o n
D e s c r i p t i o n
Displays the state of the intelligent
input terminals:
7
Terminal numbers
Displays the state of the intelligent
output terminals:
Displays the output frequency scaled
by the constant in b086.
Decimal point indicates range:
0 to 3999
Displays the actual frequency, range
is -400 to 400 Hz
Displays the torque command, range
is -200 to 200 %
Displays the torque bias value, range
is -200 to 200 %
Displays the output torque, range is
-200 to 200 %
Voltage of output to motor,
Range is 0.0 to 600.0V
Displays the input power, range is 0
to 999.9 kW
Displays watt-hour of the inverter,
Range is 0. to 9999.(0 to 9999) /
1000 to 9999 (10000 to 99999)/
100 to 999 (100,000 to 999,000)
Displays total time the inverter has
been in RUN mode in hours.
Range is 0. to 9999.(0 to 9999) /
1000 to 9999 (10000 to 99999) /
100 to 999 (100,000 to 999,000)
Displays total time the inverter has
been powered up in hours.
Range is 0. to 9999.(0 to 9999) /
1000 to 9999 (10000 to 99999) /
100 to 999 (100,000 to 999,000)
Temperature of the cooling fin, range
is -20~150
Displays the state of lifetime of
electrolytic capacitors on the PWB
and cooling fan.
47
ON
OFF
6 5 4
3
2
1
ON
OFF
Relay
12 11
Lifetime expired
Normal
Cooling fan
Electrolytic caps
Run
Mode
Units
Edit
Hz times
constant
Hz
%
%
%
V
kW
hr
hr
C