C
ONNECTIONS
+LOAD 1,2,3,4
-LOAD 1,2,3,4
EPS Fault
GEN Fault
+BATT
-BATT
S
O
IGNALLING
UTPUTS
GEN Fault (general)
EPS Fault (mains)
Lid Tamper
+ve voltage output to load equipment
-ve voltage output to load equipment
Voltfree contacts for loss of mains indication
Voltfree contacts for general faults (see signalling outputs)
+ve (Red lead) connection to standby battery
-ve (Black lead) connection to standby battery
Open when battery disconnected, *output fuse fail,
battery fuse fail or output short circuit. (*Applies only to
O/P 1 of multiple fused units).
Rating: 0.1A @ 60V dc N/O volt free contact.
Open when loss of mains for more than 10s.
Rating: 0.1A @ 60V dc N/O volt free contact.
Note: Contact open in when lid opened by normal
means or unit is removed from mounted surface
Rating: 3A @ 125V ac N/O volt free contact.
PAK200467-HW_01A March 2020