Max Output Current to load
Output Fuses* (20mm glass)
Max Mains Input Current (at
90V ac)
Mains Input Fuse
(20mm 250Vac HBC)
Battery Fuse Protection
L
I
OCAL
NDICATORS

Local Indicators

MAINS LED (Green)
FAULT LED (Red)*
*For 10A model, only one Fault LED will be visible via front panel. Each module has
independent fault monitoring and signalling.
Model Specification Table
PS-HL-13805BM-4OP
5A
F5.0A (4 x 1.25A)
2.0A
T3.15A
F5.0 A
Mains present
Flashes (1s period) when: loss of mains, battery
disconnected, output fuse fail, battery fuse fail, output
short circuit or low output voltage
PAK200467-HW_01A March 2020
PS-HL-13810BM-8OP
2 x 5A
2 x F5.0A (8 x 1.25A)
3.0A
T3.15A
2 x F5.0A