Honeywell RAE Systems RAEPoint User Manual page 40

Multi-function wireless infrastructure component
Table of Contents

Advertisement

3- Hazardous Location Classification
Hazardous Areas Classified by Zones
RAEPoint is intended to be used in hazardous areas classified for Zone 1 or Zone 2, within the
temperature range of -20°C to +55°C, where gases of explosion groups IIA, IIB or IIC and T6 may be
present.
Hazardous Areas Classified By Divisions
RAEPoint is intended to be used in hazardous areas classified for Class I Div. 1 or 2, within the
temperature range of -20ºC to +55ºC, where gases of explosion groups A, B, C or D and
temperature class T6 may be present.
4- Instructions For Safe Use
The threaded coaxial connector external to the enclosure shall only be fitted with a dedicated
antenna and shall not be used to supply an external, intrinsically safe circuit.
5- Connections And Ratings
Input/Output
The rated RAEPoint input/output are as follows:
Input: 2.4W
V
: 12-28VDC
input
6- Maintenance
Installation and Access Instructions
An explosion-proof seal is required for all gas groups within 18" (46 cm) of the enclosure.
l
The appropriate regulations for installation, service and repair must be properly observed
during such activities.
To prevent ignition of hazardous atmospheres, area must be free of flammable vapors and
l
supply circuit must be disconnected before removing cover.
Negative terminal of power supply must be grounded.
Honeywell® RAEPoint |
User Manual
WARNING
40