Honeywell NOTIFIER N-ANN-80 Series Product Installation Document page 2

Advertisement

N-ANN-80 Series
B (ANN-BUS)
A (ANN-BUS)
+ (24 VDC)
- (GND)
Figure 3 Wiring the N-ANN-80(-W) to an FACP
B (ANN-BUS)
A (ANN-BUS)
+ (24 VDC)
- (GND)
N-ANN-80C
Figure 4 Wiring the N-ANN-80C to an FACP
Notes for Figure 3 and Figure 4:
1.
All connections/sources must be power-limited and supervised.
2.
12 - 22 AWG (0.33 - 3.31 mm2) wire for N-ANN-80(-W) and 12-
18 AWG (0.75 - 3.25 mm2) for N-ANN-80C is acceptable for the
24 VDC circuit.
3.
Power wire distance limitation is set by 1.2 volt maximum line drop
from source to end of circuit.
4.
Maximum distance from FACP to last ANN-BUS device must not
exceed 6,000 feet (1,800 m). Refer to the Wiring Distance Table in
the appropriate FACP manual for wire gauge and distance
limitations.
2
}
Connect to FACP ANN-BUS
and/or next device
}
Connect to FACP or UL Listed
Power Supply for Protective
Signaling and/or next device
2
}
Connect to FACP ANN-BUS
and/or next device
}
Connect to FACP or UL Listed
Power Supply for Protective
Signaling and/or next device
Setting the DIP Switches - N-ANN-80(-W)
Address Setting
Each ANN-BUS device requires a unique address. DIP switches 1-4 on
S1 are used to set the address. This address will be displayed on the LCD
display as the Station ID number.
A maximum of 8 devices can be connected to the FACP ANN-BUS
communication circuit. ANN-BUS device addresses do not need to be
sequential and can be set to any number between 01 and 08. Note that 00
is not a valid address. The following illustrates the DIP switch settings
for each address (ID Number).
ID Number
(Address)
(not valid) 00
01
02
03
04
05
06
07
08
Communication Protocol
DIP switch 5 is used to determine the communication protocol of the N-
ANN-80 Series. Set DIP switch 5 to ON for ANN-BUS protocol. Set
DIP switch 5 to OFF for AIO protocol.
1 2 3 4 5 6 7 8
ANN-BUS protocol
End-of-Line Resistor
The end-of-line termination resistor must be enabled at S1 on the last
device on the communication circuit. All other annunciators should have
these switches set to disable.
1 2 3 4 5 6 7 8
termination enabled
DIP switches 7 and 8 are unused.
N-ANN-80 Series Installation Document — P/N 52986:C3 12/6/2022
DIP Switch S1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
AIO protocol
1 2 3 4 5 6 7 8
termination disabled

Advertisement

loading

This manual is also suitable for:

Fire-lite alarms ann-80 series