Download Print this page

Honeywell 315-080 Product Installation Document page 2

Remote fire annunciator

Advertisement

Wiring the 315-080 to the FACP
Refer to Table 1 and Figure 3 for wiring connections.
315-080 Terminals
(TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
315-080 Terminals
(TB2)
Terminal 1
Table 1 315-080 to FACP Connections
315-080
B (COMM-BUS)
A (COMM-BUS)
+ (24 VDC)
- (GND)
Figure 3 Wiring the 315-080 to an FACP
Notes:
1.
All connections/sources must be power-limited and supervised.
2.
12 - 22 AWG (0.33 - 3.31 mm2) wire for 24 VDC circuit is
acceptable.
3.
Power wire distance limitation is set by 1.2 volt maximum line drop
from source to end of circuit.
4.
Maximum distance from FACP to last COMM-BUS device must
not exceed 6,000 feet (1,800 m). Refer to the Wiring Distance Table
in the appropriate FACP manual for wire gauge and distance
limitations.
2
FACP EIA-485
Terminals
(-)
(+)
A (COMM-BUS)
B (COMM-BUS)
FACP EIA-485
Terminals
Earth Ground
}
Connect to FACP COMM-BUS
and/or next device
}
Connect to FACP or UL Listed
Power Supply for Protective
Signaling and/or next device
2
315-080 Remote Fire Annunciator Installation Document — P/N LS10226-001HM-E:B 5/31/2022
Setting the DIP Switches
Address Setting
Each ANN-BUS device requires a unique address. DIP switches 1-4 on
S1 are used to set the address. This address will be displayed on the
LCD display as the Station ID number.
A maximum of 8 devices can be connected to the FACP COMM-BUS
communication circuit. COMM-BUS device addresses do not need to be
sequential and can be set to any number between 01 and 08. Note that 00
is not a valid address. The following illustrates the DIP switch settings
for each address (ID Number).
ID Number
(Address)
(not valid) 00
01
02
03
04
05
06
07
08
Communication Protocol
DIP switch 5 is used to determine the communication protocol of the
315-080. Set DIP switch 5 to ON for COMM-BUS protocol. This switch
must stay in the ON position for proper functionality.
1 2 3 4 5 6 7 8
Ensure switch 5 is ON
End-of-Line Resistor
The end-of-line termination resistor must be enabled at S1 on the last
device on the communication circuit. All other annunciators should have
these switches set to disable.
1 2 3 4 5 6 7 8
termination enabled
DIP switches 7 and 8 are unused.
DIP Switch S1
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
termination disabled

Advertisement

loading