Monitored Data - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 511 557-UEN Rev. A
Table 36:
SSCPOW Non group settings (advanced)
Name
Values (Range)
CmdOffTime
MaxContDelay
POWCapSet
Table 37:
SSCPOW Group settings (advanced)
Name
Values (Range)
ByPassMode
ContingencyMode
CloseStrategySrc
9.3.6

Monitored data

Table 38:
Name
LOCCNTRL
CBOPCAPL1
CBOPCAPL2
CBOPCAPL3
Table continues on next page
Technical Manual
Unit
100.0 - 950.0
ms
45.00 - 200.00
ms
N/A
-
None
Close
Open
Close & Open
Unit
No bypass
-
Close
Open
Open & Close
Block Open &
-
Close
Bypass Open &
Close
Block Open,
bypass Close
Bypass Open,
block Close
Internal
-
External control
External only
External / block
External / bypass
SSCPOW Monitored data
Type
BOOLEAN
INTEGER
INTEGER
INTEGER
© 2021 Hitachi Energy. All rights reserved.
Step
Default
1.0
100.0
1.00
50.00
-
N/A
Step
Default
-
No bypass
-
Bypass Open &
Close
-
Internal
Values (Range)
Unit
0=Remote
-
1=Local
1=None
-
2=Open
3=Close-Open
4=Open-Close-
Open
5=Close-Open-
Close-Open
1=None
-
2=Open
3=Close-Open
4=Open-Close-
Open
5=Close-Open-
Close-Open
1=None
-
2=Open
3=Close-Open
4=Open-Close-
Open
5=Close-Open-
Close-Open
Description
Duration of output commands
Alarm threshold for maximum controller
delay time
Point on wave capability of circuit
breaker
Description
Bypass open or close operations -
overrules CntrldOperType
Actions to take in case controlled
switching is not possible
Closing strategy source and fallback to
be applied based on EXTSTGY
PID-7616-MONITOREDDATA v2
Description
Local control indication
Circuit breaker operating capability for
phase L1
Circuit breaker operating capability for
phase L2
Circuit breaker operating capability for
phase L3
Section 9
Control
77