Signal Identification - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 13
Station communication
GUID-938F229C-5768-4DF9-B3B6-78A52266F643 V1 EN-US
Figure 159: Example of signal path for sampled analog values from MU and conventional
13.7.6.1

Signal identification

Up to four logical MUs can be connected to an IED on a single physical interface. The data streams
from individual MUs are distinguished by the SVId (Sampled Values Identification) setting, which
must be set identical to the MsvID data attribute of MSVCB01 in the MU.
The IEC 61850-9-2(LE) guideline specifies that the value of SVId shall comprise 10 characters and
follow the convention "xxxxMUnn01". The portions "xxxx" and "nn" can be substituted by user-defined
358