Signals

Table 238: CBCOMP Input signals
Name
BLOCK
IDCLL1
IDCLL2
IDCLL3
IDCLIL1
IDCLIL2
IDCLIL3
IDOPL1
IDOPL2
IDOPL3
IDOPIL1
IDOPIL2
IDOPIL3
CVCLT
CVOPT
TMPCLL1
TMPCLL2
TMPCLL3
TMPOPL1
TMPOPL2
TMPOPL3
PRCLL1
PRCLL2
PRCLL3
Table continues on next page
238
Type
Default
Description
BOOLEAN
0
Block binary outputs
GROUP
-
Idle time (mechanical status based) compensation value for
SIGNAL
closing CB pole L1
GROUP
-
Idle time (mechanical status based) compensation value for
SIGNAL
closing CB pole L2
GROUP
-
Idle time (mechanical status based) compensation value for
SIGNAL
closing CB pole L3
GROUP
-
Idle time (current based) compensation value for closing CB pole
SIGNAL
L1
GROUP
-
Idle time (current based) compensation value for closing CB pole
SIGNAL
L2
GROUP
-
Idle time (current based) compensation value for closing CB pole
SIGNAL
L3
GROUP
-
Idle time (mechanical status based) compensation value for
SIGNAL
opening CB pole L1
GROUP
-
Idle time (mechanical status based) compensation value for
SIGNAL
opening CB pole L2
GROUP
-
Idle time (mechanical status based) compensation value for
SIGNAL
opening CB pole L3
GROUP
-
Idle time (current based) compensation value for opening CB pole
SIGNAL
L1
GROUP
-
Idle time (current based) compensation value for opening CB pole
SIGNAL
L2
GROUP
-
Idle time (current based) compensation value for opening CB pole
SIGNAL
L3
GROUP
-
Control voltage compensation value for close
SIGNAL
GROUP
-
Control voltage compensation value for open
SIGNAL
GROUP
-
Temperature compensation value for closing CB pole L1
SIGNAL
GROUP
-
Temperature compensation value for closing CB pole L2
SIGNAL
GROUP
-
Temperature compensation value for closing CB pole L3
SIGNAL
GROUP
-
Temperature compensation value for opening CB pole L1
SIGNAL
GROUP
-
Temperature compensation value for opening CB pole L2
SIGNAL
GROUP
-
Temperature compensation value for opening CB pole L3
SIGNAL
GROUP
-
Drive pressure compensation value for closing CB pole L1
SIGNAL
GROUP
-
Drive pressure compensation value for closing CB pole L2
SIGNAL
GROUP
-
Drive pressure compensation value for closing CB pole L3
SIGNAL