Section 17
Technical data
17.11
Environmental conditions and tests
Table 435: Environmental conditions
Description
Operating temperature range
Short-time service temperature range
Relative humidity
Altitude
Transport and storage temperature range
Table 436: Environmental tests
Description
Cold tests
Dry heat tests
Damp heat tests
17.12
Electromagnetic compatibility tests
Table 437: Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
•
Common mode
•
Differential mode
Electrostatic discharge test
•
Contact discharge
•
Air discharge
Radio frequency interference tests
•
Conducted, common mode
Table continues on next page
436
Type test value
operation
96 h at -25ºC
16 h at -40ºC
storage
96 h at -40ºC
operation
16 h at +70ºC
storage
96 h at +85ºC
steady state
240 h at +40ºC
humidity 93%
cyclic
6 cycles at +25 to +55ºC
humidity 93...95%
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
© 2021 Hitachi Energy. All rights reserved.
Value
-25...+55ºC (continuous)
-40...+70ºC (<16h)
Note: Degradation in MTBF and HMI performance
outside the temperature range of -25...+55ºC
<93%, non-condensing
up to 2000 m
-40...+85ºC
Reference
IEC 60068-2-1
ANSI C37.90-2005 (chapter 4)
IEC 60068-2-2
ANSI C37.90-2005 (chapter 4)
IEC 60068-2-78
IEC 60068-2-30
Reference
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2012
IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
IEC 61000-4-6 , level 3
IEC 60255-22-6
1MRK 511 557-UEN Rev. A
D0E7972T201305151403 v2
D0E7974T201305151403 v2
Technical Manual