Table 435: Environmental conditions
Description
Operating temperature range
Short-time service temperature range
Relative humidity
Altitude
Transport and storage temperature range
Table 436: Environmental tests
Description
Cold tests
Dry heat tests
Damp heat tests
17.12

Electromagnetic compatibility tests

Table 437: Electromagnetic compatibility tests
Description
100 kHz and 1 MHz burst
disturbance test
Common mode
Differential mode
Electrostatic discharge test
Contact discharge
Air discharge
Radio frequency interference tests
Conducted, common mode
Table continues on next page
436
Type test value
operation
96 h at -25ºC
16 h at -40ºC
storage
96 h at -40ºC
operation
16 h at +70ºC
storage
96 h at +85ºC
steady state
240 h at +40ºC
humidity 93%
cyclic
6 cycles at +25 to +55ºC
humidity 93...95%
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (emf), f=150 kHz...80 MHz
© 2021 Hitachi Energy. All rights reserved.
Value
-25...+55ºC (continuous)
-40...+70ºC (<16h)
Note: Degradation in MTBF and HMI performance
outside the temperature range of -25...+55ºC
<93%, non-condensing
up to 2000 m
-40...+85ºC
Reference
IEC 60068-2-1
ANSI C37.90-2005 (chapter 4)
IEC 60068-2-2
ANSI C37.90-2005 (chapter 4)
IEC 60068-2-78
IEC 60068-2-30
Reference
IEC 61000-4-18, level 3
IEC 60255-22-1
ANSI C37.90.1-2012
IEC 61000-4-2, level 4
IEC 60255-22-2
ANSI C37.90.3-2001
IEC 61000-4-6 , level 3
IEC 60255-22-6
1MRK 511 557-UEN Rev. A
D0E7972T201305151403 v2
D0E7974T201305151403 v2