Telephone Requirements - Honeywell DACT-E3 Product Installation Document

Digital alarm communicator transmitter
Table of Contents

Advertisement

Code
Event
927
DACT Report Time out
928
DACT Account 2 Fault
929
DACT Line 1 Fault
930
DACT Line 2 Fault
931
INI Communication Fault
932
INI Node Number Fault
933
Net Port 1
934
Net Port 2
935
Fan Restart
936
User 1
937
User 2
938
User 3
939
User 4
940
User 5
941
Node 0
942
Reserved
943
Releasing Zone 1
944
Releasing Zone 2
945
Releasing Zone 3
946
Releasing Zone 4
947
Releasing Zone 5
948
Releasing Zone 6
949
Releasing Zone 7
950
Releasing Zone 8
951 - 981
Cross Zone 1 - 31
982
Node Missing
983
Node Extra
984
LCD Display Fault
985
Any ASM-16 or ANU-48
986
Any non-SLC Event
987-990
Reserved
991
Test with exception
992 - 999
Reserved
Table 4.3.1 Non-SLC Device Events Reporting Codes (Continued)

4.4 Telephone Requirements

DC Ringer Equivalence Number (REN) = 0.5B •
The REN is used to determine the quantity of devices that may be connected to the telephone line. Excessive RENs on the telephone
line may result in the devices not ringing in response to an incoming call. In most, but not all areas, the sum of the RENs should not
exceed five. To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the
Telephone Company to determine the maximum REN for the calling area.
NOTE: Communication Line Test Requirement:
To comply with UL 864 10th Edition, the System self-tests the communication line between the communicator and the
receiver, 4-24 DACT Test Time Settings per day.
DACT-E3 Product Installation Document — P/N 9000-0581:J6 12/16/2019
Issued if node address DIP switches do not match the node number in the node's
configuration.
Cross Zone 31 (981) is used to report Group Cross Zone Events.
Any Node Missing Trouble, does not indicate a specific node
Any Node Extra Trouble does not indicate a specific node
Any LCD Display Fault (LCD-E3, LCD-7100 or LCD-SLP) (does not indicate a specific
display
Does not indicate a specific ASM-16 or ANU-48
Any non-SLC Event that is not otherwise listed in the Table.
Automatic DACT test OK, but Trouble, or Off-Normal condition present in the system.
AC Ringer Equivalence Number = 1.3 •
Comments
Complies with FCC Part 8
13

Advertisement

Table of Contents
loading

Table of Contents