FF-SRT Series
SPECIFICATIONS
General technical data
Available time ranges
Repeatability precision
Input
Nominal consumption
Nominal frequency
Output
Contact complement
Switching Capability
Current Range (min. to max.)
Voltage Range (min. to max.)
Typical Electrical Life Expectancy
Typical Power Factor (cos
Operating frequency
General
Temperature range
Vibration resistance
Conductor connection
Conductor attachment
Install
arc
NOTE
1:
suppression device across
load
to
avoid
module
contact arcing and ensure
specified
relay
life
expectancy.
NOTE 2:
Total operations =
Operations at power factor
1 multiplied by the limitation
factor. If the power factor
is 0.5 at 230 VAC, 2A
(300,000 operations), the
limitation factor is 0.70.
300,000 x 0.70 = 210,000
total operations.
2
Nominal voltage
Contact type
DC
AC
2A
5A
8A
ϕ ϕ
)
0.3
0.5
0.7
1.0
Fuse rating
Mechanical life
Sealing
Housing material
2
2 x 2,5 mm
Mounting
Weight
FIG 1.
CONTACT LIFE FOR 100%
RESISTIVE LOAD (typical)
(note 1)
power factor = 1 (cos
Adjustable 1 channel: SRT _ _ 1R: 0,3 to 1 sec; 0,3 to 3 sec;
0,5 to 5 sec, 1 to 10 sec; 3 to 30 sec.
Fixed, 1 channel : SRT _ _ 1F: 1; 3; 5, 10 and 30 sec.
Adjustable 2 channels: SRT _ _ 2R: 0,5 - 5 sec, 1 - 10 sec.
Fixed, 2 channels: SRT _ _ 2F: 5, 10 sec.
±15 % from selected value
120 VAC (-15%, +10%), 230 VAC (-20%, +10%), 24 VDC (-10%, +20%)
Channel one model: 0.85 W, 4.5 VA; Channel two model: 1.7 W, 4.5 VA
1 NO, 1 NC contacts
Safety relay, positive-guided
Power factor = 1 with resistive load
30 mA to 8A
10 to 110 VDC
10 to 250 VAC
Power factor = 1 at 230 VAC/DC (note 1)
300,000 operations
150,000 operations
100,000 operations
Limitation Factor (note 2)
2000 switching cycles/hour (max.)
6 A gL (max.)
Ten million switching operations
°
°
°
-20
C to + 60
C (-4
F to 140
Housing IP 40; Terminals IP 20
Thermoplastic
Amplitude 0,35 mm; Frequency 10 to 55 Hz
[14 AWG] solid (max.) or 2 x 1.5 mm
Flat terminal according to DIN 46206 and DIN 57609/VDE
Quick install rail mounting DIN EN 50022-35
200 g (0.44 lb.) for VDC 350 g (0.77 lb.) for VAC
FIG 2. LIMITATION FACTOR FOR
INDUCTIVE LOADS (note 2)
power factor < 1 (cos
ϕ
)
PK 107019-01-EN FR26 GLO 398 Printed in Germany
PK 107019-01
ISSUE 1
50/60 Hz
0.45
0.70
0.85
1.00
°
F) at max. 90% humidity
2
[16 AWG] (max.) stranded wire with sleeve DIN 46288