5
Horizontal main busbar
Icw 35 kA
Quantity of support kits. Fix / Floating
Dimension
12 modules
50 x 10
2/0
60 x 10
2/0
80 x 10
2/0
100 x 10
2/0
(120x10)x2
2/0
(160x10)x2
2/0
Icw 65 kA
Quantity of support kits. Fix / Floating
Dimension
12 modules
60 x 10
2/1
80 x 10
2/1
100 x 10
2/0
(120x10)x2
2/0
(160x10)x2
2/0
Horizontal main bus bar 4000A
24 modules
36 modules
2/1
2/1
2/1
2/1
2/0
2/1
2/0
2/1
2/0
2/0
2/0
2/0
24 modules
36 modules
2/2
2/2
2/1
2/2
2/1
2/1
2/1
2/1
2/1
2/1
depth 800 mm/Max. 4000A
Icw 50 kA
Quantity of support kits. Fix / Floating
Dimension
12 modules
50 x 10
2/0
60 x 10
2/0
80 x 10
2/0
100 x 10
2/0
(120x10)x2
2/0
(160x10)x2
2/0
Icw 80 kA & 85 kA
Quantity of support kits. Fix / Floating
Dimension
12 modules
80 x 10
2/1
100 x 10
2/1
(120x10)x2
2/0
(160x10)x2
2/0
24 modules
36 modules
2/1
2/2
2/1
2/1
2/1
2/1
2/1
2/1
2/0
2/0
2/0
2/0
24 modules
36 modules
2/2
2/3
2/2
2/2
2/2
2/2
2/2
2/2