Meter Technical Specifications - Honeywell Green Class meter Installation Instructions Manual

Table of Contents

Advertisement

GREEN CLASS METER

METER TECHNICAL SPECIFICATIONS

Part number configuration
Green Class sub meter
SUBG
Input Voltage Configuration:
MAINS Voltage Input:
Input Power:
Current Sensor Rating:
Power Factor:
Line Frequency:
Metering Accuracy:
Voltage Operating Range:
Temperature Range (Standard indoor enclosure):
Temperature Range: (NEMA 4X outdoor enclosure):
Relative Humidity Range:
Altitude:
Voltage Overload:
Current Sensor Overload:
Pollution Degree:
Installation (Overvoltage) Category:
Measurement Category:
Indoor Housing Rating (Standard):
Outdoor Housing Rating (Optional):
Display Readout:
Standard Ranges:
IDR Interface Port:
Isolated Pulse/Alarm Outputs (TB5, TB6):
Recommended in-Line Fuse:
62-0340-01
Pulse
P: Pulse
4-Wire Wye, 120/208 VAC:
2 Phase, 120/240 VAC:
4-Wire Wye, 277/480 VAC:
3-Wire Delta, 220/240 VAC:
3-Wire Delta, 480 VAC:
Cable Specificatons:
Input/Output Voltage:
Cable Connector:
Ckt Input Isolation:
Ckt Output Isolation:
Output Voltage Potential:
Mating Plug Connector:
Signal Isolation Voltage:
Manufacturer:
Mfg Part No.:
Rating:
Voltage
208: 208 Volts
480: 480 Volts
600: 600 Volts
3-Wire (Delta) or 4-Wire (Wye)
Up to 480 VAC RMS Available
6VA Maximum Rating
Up to 3200 Amp RMS AC Available
.5 leading or lagging
50-60 Hz
Certified to ANSI C12.16 (+/- 1% from 1% to 100% of rated load)
+/- 10% of rated load
-20 degrees C to +50 degrees C
-20 degrees C to +70 degrees C
0-95% Non-Condensing
2000 meters maximum
+25% Continuously; +100% for 20 Cycles
100% for 1 minute without damaging meter
Degree 2 in accordance with IEC 664
Category III
Category III
NEMA 12
NEMA 4X
KWh Accumulated, cost to date, Instantaneous kW, projected
hourly cost, total CO2 emissions, projected hourly CO2
emissions
100, 200, 400, 800, 1600 and 3200 Amp
100, 200, 400, 800, 1600 and 3200 Amp
100, 200, 400, 800, 1600 and 3200 Amp
100, 200, 400, 800, 1600 and 3200 Amp
100, 200, 400, 800, 1600 and 3200 Amp
UL Listed/Rated Telephone Cord, 6-conductor
300 VAC, stranded conductors, 22-26 AWG.
+5 VDC/18 VAC
RJ-45 male IDC
5.3K VAC for 1 Minute
2.5K VAC
0 VDC to +5 VDC Logic Levels
Weidmuller PN: 152876
5.3K VAC for 1 Minute
Littlefuse
KLDR.100
100mA, Time Delay, 600 VAC Cartridge Fuse
18
Current
100: 100 Amps
200: 200 Amps
400: 400 Amps
800: 800 Amps
1600: 1600 Amps
3200: 3200 Amps