Test input example 4:
Mutual exclusion mode using two FF-SLG18 / FF-SLG30 type 2 safety light curtains with test input and an
auxiliary safety switch (optional) (modes 92 and 93)
(dc+)
Fuse
1 A
0,5 A
1 A
max.
max.
2
3
6
(+)
Test
FF-SLG
FF-SLG
(-)
receiver
emitter
1
7 1
4
6
A1+
S11 S12 S14 S13
-
+ +
FF-SRM200P2
A2-
(dc-)
Note (A):
Connect test output terminal 58 to the test input of each FF-SGL18 / FF-SLG30 emitter as shown in the wiring diagram above while
respecting the polarity of the test input terminals (test input (+) = terminal 6, test input (-) = terminal 1).
Note (B):
Auxiliary safety device for robot position (use is application depending and may be optional):
When a safety switch (that typically does not have a test input) is used as robot position sensor, connect the test output terminal 58
as shown above, in order to ensure the switch being also tested.
When no robot position sensor is used, connect the unused terminals to power and to the test output: S31 to (dc-); S32 to 58.
107111-11-EN FR26 GLO 503 Printed in Germany
1 A
0,5 A
Fuse
max.
max.
1 A
2
3
Test
(+)
(A)
(A)
FF-SLG
FF-SLG
(-)
receiver
emitter
5
7 1
4
6
5
auxiliary
safety device
for robot
position (B)
S21 S22 S24 S23
-
-
+ +
-
13 23
48
K3
Fuses
muting error /
6 A max.
restart
Acknowledge
6
P/B
1
K4
K3
(D)
S31
S32
S34 S33
S41 S42 S44 S43
-
+ +
-
-
+ +
K1
K2
24 14
58
test output
machine
control
K4
(A)
Start
-
(B)
23