Mounting, demounting and electric installation
VESA attachment with four M4 threaded bolts (75 mm × 75 mm)
Cable bushings, appropriate for ready-made cables
Fig. 10-7: Position of VESA fastening screws and cable bushings

10.4.2 VESA support arm

The operator terminals VEP 30.5DPU... can be attached to a standardized VESA
support arm provided by different manufacturers.

10.5 Electric connection

DANGER
The 24 V DC input voltage must comply with the requirements of the "safe sepa-
ration"!
Plug and remove the plug connection only if there is no voltage!
NOTICE
Use only shielded cables and metallic, conductive connector or coupling hous-
ings with large-area shield support.
Interfering AC voltage components - such as the ones resulting from an uncon-
trolled three-phase bridge circuit without smoothing and with a ripple factor
(see DIN 40110/10.75, section 1.2) of 5 % - are allowed.
24/41
Embedded Terminals with Profibus DP
Lethal danger without safe separation!