Programming
NOTE: The system must be monitored by a Supervising Station when using carbon monoxide detection per The Requirements for the
Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720.
The programmer can continue adding detectors by pressing the ESC key which will return the display to the Add Detector Screen.
Delete Detector
DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such
as 005. When the last digit is keyed-in, the following screen will be displayed:
The programmer can continue deleting detectors by pressing the ESC key which will return the display to the Delete Detector Screen.
Edit Detector
The programmer can change a detectors existing or factory default programming by pressing 3 in the Detector Screen. The following
screen will be displayed:
A flashing cursor will appear in the position of the first asterisk to the left. The programmer keys in the three digit detector address, such
as 017.
When the last digit is keyed-in, if the selected address has not been added to programming, a screen showing information about a device
that is installed with a lower address, closest to the selected address, will be displayed.
If no detectors have been installed on the loop, the following will be displayed:
If the selected address has been added to programming, device summary screens will be displayed. These screens allow the programmer
to view all device settings at a single glance. Pressing the left or right arrow keys will allow the programmer to rapidly view the devices
at the previous or next address (if installed).
If a detector (such as a photoelectric detector) with the selected address is not physically installed on the SLC or has a communication
fault but the address is programmed in the system, the following screen will be displayed:
If the selected address has been added to programming and a detector (such as a photoelectric detector) with the selected address is phys-
ically installed on the SLC and is communicating with the control panel, the following will be displayed:
To change the programming for the displayed detector, press the keyboard 'down' arrow key to view the Edit Detector screens.
In the preceding example:
54
Pressing 2 in the Detector Screen will display the Delete Detector Screen which allows the programmer to
delete a specific detector:
DELETE DETECTOR
ENTER DETECTOR#

Delete Detector Screen
DELETE DETECTOR
DETECTOR#
IS DELETED
EDIT DETECTOR
ENTER POINT ADDRESS

Edit Detector Screen
NO DETECTOR
Edit Detector Screen #1
TROUBL SMOKE(PHOTO)
<ADJ><NOUN>
Edit Detector Screen #1
NORMAL SMOKE (PHOTO)
<ADJ><NOUN>
Edit Detector Screen #1
005
INSTALLED
ZNNN
1D017
ZNNN
1D017
V 
NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018