Backup Battery Sensor Connections

Figure 4-29 Backup Battery Sensor Connections on Expansion Cabinet Junction Panel

Procedure 4-8 How to Connect Backup Battery Sensor to the Equipment Cabinet
1
2
4-30
Make sure all power to the Power Supply Unit is off to prevent accidental
contact with high energy and injury to personnel.
Plug the temperature sensor cable (Motorola P/N 0166501N84) into the 2-pin connector on one
side and attach the sensor to the backup battery according to the manufacturer's instructions,
which are supplied with the accessory kit. See

Figure 4-30 Backup Battery Temperature Sensor Cable

Make AC cable connection between the facility AC outlet and AC connector on the junction
panel using plug (Motorola P/N 3166502A01 for MTS 2 and Motorola P/N 3166502A02 for
MTS 4) as described in
"110 VAC – 240 VAC Input Power
Chapter 4: Hardware Installation
Figure
4-30.
Connections".
6802800U74-N September 2009