1.1.1
LED indicators
1. Fire (zone)
When the red LED is activated the indicated zone is in alarm status. A flashing LED
indicates that a detector has activated the alarm. A constant LED indicates that a manual
call point has activated the alarm.
2. Fault / Test / Disabled (zone)
A flashing yellow LED indicates a fault in the zone. A constant LED means the zone is
either disabled or in test mode.
3. Supply ON
A green LED indicates that the system is powered up.
4. Fire (general)
A red LED indicates a zone is in alarm status. A flashing LED indicates that a detector
has activated the alarm. A constant LED indicates that a manual call point has activated
the alarm.
5. Fault (general)
A flashing yellow LED indicates a fire system fault.
6. Disabled
A zone or sounder has been disabled.
7. Maintenance
For installations using Clean-Me enabled detectors only. A yellow LED indicates detector
maintenance is required. The detector zone is displayed when the Silence Buzzer key is
pressed for more than one second. This feature is only available in standby mode.
8. Sounder Delay
A sounder delay has been programmed.
9. Sounder Fault / Disabled
A flashing yellow LED indicates a fault in one of the sounder outputs. A constant LED
indicates that the sounders have been disabled.
10. System Fault
A fault in the fire panel has been detected.
11. Supply Fault
Indicates a power supply fault – mains, batteries or fuse.
12. Out of Service
The fire panel has lost power and battery voltage is below the minimum value (22 VDC).
13. Silence Buzzer
The fire panel buzzer has been silenced pressing the Silence Buzzer button.