Download Print this page
GE ARITECH FP400 Series User Manual
GE ARITECH FP400 Series User Manual

GE ARITECH FP400 Series User Manual

Conventional microprocessor controlled fire detection and alarm panels
Hide thumbs Also See for ARITECH FP400 Series:

Advertisement

Quick Links

FP400 Series
Conventional microprocessor
controlled fire detection and
alarm panels
User Guide
Version 2.3 / June 2004

Advertisement

loading

Summary of Contents for GE ARITECH FP400 Series

  • Page 1 FP400 Series Conventional microprocessor controlled fire detection and alarm panels User Guide Version 2.3 / June 2004...
  • Page 2 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea © 2004 GE Interlogix B.V.. All rights reserved. GE Interlogix B.V. grants the right to reprint this manual for internal use only. GE Interlogix B.V. reserves the right to change information without notice.
  • Page 3: Table Of Contents

    ABLE OF ONTENTS User Guide ............................. 4 Description of control panel......................4 What to do in case of a fire or fault ..................... 9 Maintenance............................10 System maintenance........................10 Battery maintenance ........................10 Cleaning ............................10 Troubleshooting ..........................11 FP400 Series User Guide...
  • Page 4: User Guide

    UIDE 1.1 Description of control panel Figure 1: FP416 Front Panel Figure 2: FP404 Front Panel FP400 Series User Guide...
  • Page 5 1.1.1 LED indicators 1. Fire (zone) When the red LED is activated the indicated zone is in alarm status. A flashing LED indicates that a detector has activated the alarm. A constant LED indicates that a manual call point has activated the alarm. 2.
  • Page 6 14. Sounders ON The sounders have been activated. If the LED flashes the sounders will be activated after the programmed delay. 15. Sounders Silence The sounders have been silenced by pressing the Sounders Silence / Disable button. 16. Test A zone is in test mode. 1.1.2 Accoustic indicators Alarm indicator: Continuous internal buzzer.
  • Page 7 When the fire panel is in standby mode the Supply ON LED is activated. If a sounder delay has been programmed the Sounder Delay LED will also be activated. There are no acoustic signals. Alarm When the fire panel detects any alarm situation it will be indicated as follows: The general Fire LED will be activated.
  • Page 8 Disabled status The fire panel allows the enable and disablement of each zone independently by pressing the corresponding zone disable button. When a zone is disabled, none of the indications or events that may occur within the zone will be reported to the fire panel. It is therefore important to limit the usage of this feature.
  • Page 9: What To Do In Case Of A Fire Or Fault

    HAT TO DO IN CASE OF A FIRE OR FAULT This fire system has been designed to guarantee a quick and efficient reaction in case of alarm. To achieve this, the fire panel checks all the devices connected to it constantly, making sure that the installation is correct and providing signals in order to warn users in case of any event or abnormality.
  • Page 10: Maintenance

    AINTENANCE 3.1 System maintenance To guarantee correct functioning of the system and compliance with EN-54 standards, the following checks are recommended: Daily Verification Check that the system is in ready status. If the above is not so, take the appropriate measures.
  • Page 11: Troubleshooting

    ROUBLESHOOTING Indication Cause Action The service LED indicator is The panel has no power. Check power supply (110 or 230 OFF. VAC). Check power supply fuse. Check battery. Check battery fuse. The general fault and power The panel has no power supply Check power supply (110 or 230 supply failure LED indicator is on from the mains and is working...
  • Page 12 1048556...