GE ARITECH FP400 Series Installation Manual

Conventional microprocessor controlled fire detection and alarm panels
Hide thumbs Also See for ARITECH FP400 Series:

Advertisement

Quick Links

FP400 Series
Conventional microprocessor
controlled fire detection and
alarm panels
Installation Manual
Version 2.3 / June 2004

Advertisement

Table of Contents
loading

Summary of Contents for GE ARITECH FP400 Series

  • Page 1 FP400 Series Conventional microprocessor controlled fire detection and alarm panels Installation Manual Version 2.3 / June 2004...
  • Page 2 Aritech is a GE Interlogix brand. http://www.geindustrial.com/ge-interlogix/emea © 2004 GE Interlogix B.V.. All rights reserved. GE Interlogix B.V. grants the right to reprint this manual for internal use only. GE Interlogix B.V. reserves the right to change information without notice.
  • Page 3: Table Of Contents

    ONTENTS Introduction............................4 Package contents.......................... 4 Regulations ........................... 4 Compatibility..........................4 Series overview..........................5 Installation guide ........................... 7 Installation ............................. 7 Electrical connections ........................8 Configuration..........................14 Master modules........................... 16 System start-up ........................... 17 System check..........................17 System power-up ........................17 Functional test..........................
  • Page 4: Introduction

    NTRODUCTION The range of FP400 fire alarm and detection panels has five models: FP402 of two zones, FP404 of four zones, FP408 of eight zones, FP412 of twelve zones and FP416 of sixteen zones. The series has been designed to cover the needs of small to mid-sized installations such as schools, homes, shops, small and medium-size businesses, etc.
  • Page 5: Series Overview

    1.4 Series overview This conventional fire panel series has two different housing sizes: Small size: for 2 or 4 zones (FP402 or FP404). Large size: for 8, 12 or 16 zones (FP408, FP412 and FP416). Figure 1: FP416 layout Figure 2: FP404 layout FP400 Series Installation Manual...
  • Page 6 1. Mains connector (110 VAC / 230 8. Configuration DIP switch VAC) 9. 5 A battery fuse 2. Zones connectors (from 2 to 4, or 8, 10. Transformer connector 12 or 16, depending on fire panel model) 11. Front panel connector 3.
  • Page 7: Installation Guide

    NSTALLATION GUIDE This product has been developed in compliance with the EN54-2 and UN54-4 (UNE 23007) standard and have approvals pending. It must be installed by qualified personnel, taking into account the EN54-14 (UNE 23007-14) standard as well as the corresponding local authority’s laws.
  • Page 8: Electrical Connections

    2.2 Electrical connections WARNING! The 110 VAC or 230 VAC power must be connected to the power supply through an external magneto-thermal switch. The mains cable should have a minimum section of 1.5 mm². To avoid possible short circuits and interference, the mains cable must be kept away from the zone connection cables and from the communication ports.
  • Page 9 In installations with potential radio frequency interference, the use of a twisted, screened cable is recommended. Connect the cable screen to the cable adapter and ensure that the installation is properly connected to earth. 2.2.1 Mains power connection Figure 7: Location of bipolar magneto-thermal switch 1.
  • Page 10 Figure 8: Mains power connection 1. Mains fuse 2. Mains fuse 3. Neutral 4. Clamp 2.2.3 Connecting batteries The FP400 panels require 2 x12 V batteries of 2.6 Ah for the FP402 and FP404, and 2 x 12 V 7 Ah for FP408, FP412 and FP416 respectively. These are connected in series in order to obtain 24 VDC.
  • Page 11 2.2.4 Connecting zones A zone output can only monitor a maximum of 20 detectors or 32 manual call points. Every f zone has only one origin and one end. The last detector or call point must therefore include a 4k7 Ohm end-of-line resistor. It is not allowed to do T-offs of the line or place the end-of-line resistor in the zone output on the main circuit board.
  • Page 12 2.2.6 Connecting manual call points This fire panel is compatible with all Aritech manual call points. Compatibility with third party products cannot be guaranteed. Refer to your manual call point manual for more information. Some manual call points need a 100 Ohm 2W resistor in serial with the normally open (NO) contact.
  • Page 13 2.2.9 Potential free relay output connection These are outputs of potential free relays that can be activated in an alarm or fault situation. The fault output is generally energized. Figure 14: Potential free relay output C NO NC C NO NC 2.2.10 Resetable 24 VDC output This output allows the connection of devices that require to be reset from their power connection (this is the case with the infra-red beams).
  • Page 14: Configuration

    Figure 16: Sounder outputs SND1 SND2 Sounder outputs The sounder output is activated and supplies 24 VDC when a zone alarm is activated due to a detector or a manual call point. If a motorized alarm bell is used a diode may need to be installed in parallel in order to avoid the effect of the inverted current Figure 17: Sounder connections 1.
  • Page 15 1. DIP switch for sounder delay configuration Any programmed delay will only be activated if the alarm is triggered by a detector. An alarm triggered by a manual call point will never be delayed. Figure 19 DIP switch sounder delay settings 1 minute delay 2 minute delay 3 minute delay...
  • Page 16: Master Modules

    Figure 21: Active EOL configuration Active EOL active Active EOL inactive Figure 22: Connection of a diode in an active end-of-line installation Active end– Zone of-line Schottky diode BAT43 The active end-of-line module is optional. 2.3.3 Configuration for remote reseting You may activate either active end-of-line resistors or remote reset mode.
  • Page 17: System Start-Up

    YSTEM START 3.1 System check Before connecting the fire panel to the main power supply check the following points. The fire panel has been properly installed. There is no short or open circuit in any of the zone lines. All end-of-line resistors are installed (see section 2.2.4) If manual call points have been installed, they have a resistor of 100 Ohm 2W in series with their contacts (see section 2.2.6) All required optional configurations (class change, potential free relays outputs,...
  • Page 18 The installer should activate all the detectors into alarm and ensure the system performs all the operations and indications that were expected. FP400 Series Installation Manual...
  • Page 19: Maintenance

    AINTENANCE Maintenance measures recommended in EN54-14 must be adopted. Maintenance to be performed by the installer or the maintenance company Quarterly Inspect the entries in the on-site register and the records of the control panel. Implement the appropriate corrective action. Check all battery connections and the battery voltages.
  • Page 20: Troubleshooting

    ROUBLESHOOTING Indication Cause Action The service LED indicator is The panel has no power. Check power supply (110 or 230 OFF. VAC). Check power supply fuse. Check battery. Check battery fuse. The general fault and power The panel has no power supply Check power supply (110 or 230 supply failure LED indicator is on from the mains and is working...
  • Page 21: Technical Specifications

    ECHNICAL SPECIFICATIONS Mechanical Box size FP402 & FP404 ....................297 x 307 x 105 mm Weight without batteries ..........................3.6 Kg Box size FP408, FP412 & FP416..................420 x 335 x 110 mm Weight without batteries ..........................6.2 Kg Cable input holes ..................... 4 x 20 mm at top of housing Environmental Working temperature ........................
  • Page 22 Auxiliary 24 VDC output Output voltage ....................18 V to 28 V (nominal of 24 VDC) Maximum current ............................. 250 mA Recommended cable....................Stranded 2-wire of 1.5 mm² Power Supply Mains voltage (230) ..................230 VAC 50 Hz / 110 VAC 60 Hz Voltage tolerance..........................+10% / -15% Power supply input ..........................
  • Page 23 Calculating battery life in standby time bc = battery capacity (FP402, FP404) = 2.6 A/h x 80% = 2.08 Ah bc = battery capacity (FP408, FP412, FP416) = 7 A/h x 80% = 5.6 Ah pa = panel current in mains fault (including all EOL resistors) (mA) pc = panel current in alarm in 1 zone (including all EOL resistors) (mA) yy = detector current (refer to detector instruction manual) (uA) zz = number of detectors in installation...
  • Page 24 Aux + sounder + pc + de = zc pc (FP408) = 145 50 + 300 + 145 + 2 = 497 Battery current (Ah) in alarm (bxa): zc x 0.5 ----------- = bxa 1000 497 x 0.5 /1000 = 0.2485 Battery life (hours): (bc - ba) ------------...
  • Page 25 FP400 Series Installation Manual...
  • Page 26 FP400 Series Installation Manual...
  • Page 27 FP400 Series Installation Manual...
  • Page 28 1050086...

Table of Contents