Honeywell CIPer 50 Installation & Commissioning Instructions page 41

Hide thumbs Also See for CIPer 50:
Table of Contents

Advertisement

Pulse Counter Specifications
Using WEBs N4, the binary inputs of the CIPer Model 50 can be configured as pulse counters (fast totalizers)
for operation in conjunction with devices equipped with an open collector output.
If the duty cycle is 50% / 50%, the pulse counter supports up to 15 Hz. Counting is done on the rising edge.
TOTALIZER
CIPer
MODEL 50 CONTROLLER – INSTALLATION AND COMMISSIONING INSTRUCTIONS
TM
closed external contact →
normal (default)
open external contact →
closed external contact →
reverse
open external contact →
Table 15. BIs of CIPer Model 50 configured as fast totalizers
Frequency
Pulse ON
Pulse OFF
Bounce
BI
DRY CONTACT
COM
FAST
Figure 32: Internal wiring of BI
max. 15Hz
min. 25ms
min. 25ms
max. 5ms
24V
open
24 VDC =
closed
0 V =
GND
41
state=1
state=0
state=0
state=1
31-00233-02