Honeywell EBI XLS MASS NOTIFICATION SYSTEM Configuration, Preset Setup, Operation page 16

Table of Contents

Advertisement

HONEYWELL EMERGENCY NOTIFICATION MANAGER
Settings:
• Mass Notification not used (Default)
• Mass Notification is a higher priority than fire
• Fire is a higher priority than Mass Notification
Fig. 19. Priority Setting - VeriFire Tools
XLS-DVC
Set the Mode and Paging Level
In the General III screen in the XLS-DVC Programming
Service of VeriFire Tools:
Select ACU, LOC, CCS, or Subsidiary from the MN Mode pull-
down menu in the XLS-DVC MN Mode box. An XLS-DVC that
is not an ACU, LOC or CCS on an MN network must be
programmed as Subsidiary, and its Associated Node Number
must be 0 (zero). Select the Paging Levels to enable the ALL
CALL buttons in the second column of the DVC-KD.
Fig. 20. XLS-DVC MN Mode Setting
SET THE INPUT CATEGORY
Following are the Programmable Audio Matrix (PAM) Input
Numbers, Default Priorities and Categories that appear for an
XLS-DVC when ACU, LOC, CCS, or Subsidiary is selected as
the XLS-DVC MN Mode. The default priorities for the first 12
inputs comply with the priorities specified in UL2572 in that at
each level ACU is the highest priority and CCS is the lowest.
DVC-KD Level buttons in the second column page as follows:
• Top button (Level 1) - always pages Inputs 1, 3, or 5,
depending on whether the XLS-DVC is an ACU, LOC or
CCS.
Second button (Level 2) - always pages Inputs 7, 9, or 11,
depending on whether the XLS-DVC is an ACU, LOC or
CCS.
• Third button (Level 3) - always pages Input 13.
39-00008-1
Input Categories are Fire, MN, General, and MN Active Tone:
• When ACU, LOC, CCS, or Subsidiary is selected as a
mode, Level 1 inputs default to the MN category, and Level
2 inputs default to the Fire category.
• "MN Active Tone" is a category (it is assigned to a
sequence, there is no default), and it must be assigned
only to the MN Active Tone message sequence (See "MN
Active Tone" on page 19".
Table 7. Default Input Priorities, MN Mode Selected
Input
Input Source
Number
1
ACU Local
Paging Level 1
2
ACU Network
Paging Level 1
3
LOC Local
Paging Level 1
4
LOC Network
Paging Level 1
5
CCS Local
Paging Level 1
6
CCS Network
Paging Level 1
7
ACU Local
Paging Level 2
8
ACU Network
Paging Level 2
9
LOC Local
Paging Level 2
10
LOC Network
Paging Level 2
11
CCS Local
Paging Level 2
12
CCS Network
Paging Level 2
13
Local General
Paging
14
Network
General
Paging
If an input categorized as MN goes active, ZF20 activates, and
can suppress fire signals for all nodes in the MN mapping
when MN is the highest priority in the system.
Navigate to the Inputs
Programming Service of VeriFire Tools. Since the XLS-DVC is
set to ACU, LOC, CCS or Subsidiary mode, the first 14 Input
16
Default
Category
Priority
1
MN
2
MN
3
MN
4
MN
5
MN
6
MN
7
Fire
8
Fire
9
Fire
10
Fire
11
Fire
12
Fire
13
General
14
General
screen in the Audio Message

Advertisement

Table of Contents
loading

This manual is also suitable for:

Emergency notification manager

Table of Contents