Download Print this page
Honeywell ExiLED Manual

Honeywell ExiLED Manual

Surface mounted

Advertisement

Quick Links

Dimensional Drawings:
ExiLED 25m
266mm
Installation:
1
click
click
4
The product contains bracket for wall mounting and spacers for ceiling mounting.
Step 1: For double sided pictogram, install the appropriate pictograms to both sides, push up until you
hear click sound. For single sided pictogram, there is one blind pictogram in the package.
Step 2: Install the retaining clip to hold the pictograms.
Step 3: Dismantle the luminaire by sliding the mounting part as shown in picture. Fasten the mounting
part (with screws from within) to either wall bracket(supplied), ceiling (with or without supplied
spacers), pendulum, wire or flag bracket.
Step 4. Drill a hole on a black grommet and pass the mains cables through it. Connect the mains cables to
terminal blocks: L for live wire, N for neutral and PE for ground. Power supply cables cross section
should be 0.8 - 3 mm . The C1 and C2 terminals are used for elBus communication optional), DALI
communication (optional), or voltage free contact (optional). Tighten the cable tie around the
cables. ATTENTION!!: Pass the tie through one (NOT two), of the available fixing holes.
Step 5: Connect the battery cable to its respective connector on the PCB.
Step 6: In case you use a module connect it on the PCB.
Honeywell Life Safety AS, Postboks 236, 1372 Asker
Surface Mounted
53mm
2
click
click
5
2
ExiLED
ExiLED 40m
366mm
3
6
http://www.hls-nordic.com
GB
53mm

Advertisement

loading

Summary of Contents for Honeywell ExiLED

  • Page 1 ATTENTION!!: Pass the tie through one (NOT two), of the available fixing holes. Step 5: Connect the battery cable to its respective connector on the PCB. Step 6: In case you use a module connect it on the PCB. Honeywell Life Safety AS, Postboks 236, 1372 Asker http://www.hls-nordic.com...
  • Page 2 The replacement must be performed by the manufacturer or a competent person. Note: If the supply cable of the luminaire is damaged, it shall exclusively be replaced by a competent person in order to avoid hazard. Honeywell Life Safety AS, Postboks 236, 1372 Asker http://www.hls-nordic.com...
  • Page 3 Technical description ExiLED M ST LED 25m 10Y 138h ExiLED M ST LED 40m 10Y 138h Part no.: 138087.10 138126.10 Operation Voltage: 220-240V AC, 50-60 Hz Maximum Power Consumption: 3.8W / 4.1VA 4.1W / 4.4VA Battery (LiFePO ): 6.4V / 0.6Ah...

This manual is also suitable for:

Exiled m st led 25m 10y 138hExiled m st led 40m 10y 138h