Honeywell NTC20k Manual page 2

Temperature / humidity transmitter

Advertisement

溫度範圍選擇設定 Set up temperature range
電壓輸出選擇 Set up voltage output (only for voltage output type)
操作方式 Operation
1. 以 SW2,SW3,SW4 調整 (Mode、zero & span)
(Mode、zero and span) Adjustment with SW2, SW3, and SW4
先將傳訊器之上蓋拆開,再按 PCB 上之 SW2,SW3,SW4 做調整
First remove the upper housing to transmitter, than select mode with SW2 and adjust value with SW3, and SW4
2.進入 Mode 選單 Start "Mode" menu
a. 同時
且持續按 SW3 及 SW4 鍵
Press simultaneously both SW3 and SW4 about 2 sec. LED starts flashing.
b. 按 SW2 鍵選擇欲調整的項目,並以 SW3 及 SW4 調整數值
Press SW2 for mode selection, SW3 and SW4 for value adjustment.
**若 LED 閃爍 10 次未以 SW2 選擇,將自動回到正常顯示 Mode 0
If LED flashes 10 times without any mode selection, it will return to
regular display (Mode 0).
**進入 Mode 後,若 25~30 秒無動作,即自動回到正常顯示 Mode 0
It will also return to regular display Mode 0 after 25~30 sec if no action occurred.
Mode 0~4:Mode 0 ~ 4 模式
LED 面板顯示操作調整
LED display
Mode 0:正常模式
可視 LED 燈號
2
Check LED
① 按 SWITCH 調整
Press SWITCH for
adjustment
使用短路夾,以 JP1-JP5 選擇溫度範圍
Define Temperature range with the jumper in JP1-JP5.
短路 short
1:
0:
溫度範圍設定選擇
Temperature range selections
0~50℃ (Default)
0~100℃
-50~50℃
使用短路夾,以 JP6-JP10 選擇電壓輸出範圍
Define voltage output measuring range with the jumper in JP6-JP10.
短路 short
1:
0:
電壓輸出選擇
Voltage output selections
0 ~ 10V (Default)
0 ~ 5V
1 ~ 5V
約 2 秒後 LED 開始閃爍
開路 open
JP5
JP4
0
1
1
0
0
0
開路 open
JP6
JP7
0
1
0
0
1
0
Mode 1 : 溼度校正模式
溼度校正(校正單位 0.1%RH
Humidity adjustment (Unit: 0.1%RH)
按一次 SW2 切換至 Mode 1,以
SW3(+)及 SW4(-)調整數值
Press SW2 one time to switch to
Mode1, SW3(+),SW4(-) for value
adjustment
LED2 燈亮
2
LED2 Lighting
2
JP3
JP2
JP1
0
-
-
0
-
-
1
-
-
JP8
JP9
JP10
0
1
0
1
0
1
1
0
1
3WIA-0B2700-060