Lifting Method - Mitsubishi Electric Y Series Installation Manual

Air-conditioners for building application inverter outdoor unit
Hide thumbs Also See for Y Series:
Table of Contents

Advertisement

7. Lifting method

[Fig. 7.0.1]
1 P200 ~ P300
Slings
(Min. 8 m x 2)
50 mm or thicker
protective pads
(two each in the front
and back)
Protective pads
(two each in the
front and back)
2 P350 ~ P450
Slings
(Min. 8m x 2)
50 mm or thicker
protective pads
(two each in the front
and back)
Protective pads
(two each in the
front and back)
8
40°
Fan guard
Sling holes
(two each in the front and back)
40°
• Use suspension ropes that will withstand the weight of the unit.
Fan guard
• When moving the unit, use a 4-point suspension, and avoid giving impacts
• Place protective pads on the unit where it comes in contact with the ropes to
• Use a 50 mm or thicker cardboard or cloth as a protective pad on the top of
• Set the angle of roping at 40˚ or less.
• Use 2 ropes that are each longer than 8 m.
Be very careful when carrying/moving the product.
- When installing the outdoor unit, suspend the unit at the specified location of
Sling holes
(two each in the front and back)
3 P500
Slings
(Min. 8m x 2)
50 mm or thicker
protective pads
(two each in the front
and back)
Protective pads
(two each in the
front and back)
Sling holes
(two each in the front and back)
to the unit (Do not use 2-point suspension).
protect the unit from being scratched.
the unit to prevent contact between the fan guard and slings.
Caution:
the unit base. Stabilize as necessary so that it does not move to the side and
support it at 4 points. If the unit is installed or suspended with 3-point support,
the unit may become unstable and fall.
40°
Fan guard

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pucy-p-ykaPucy-p-yka-bs

Table of Contents