Precautions for outdoor unit combinations
Refer to [Fig. 9.2.2] for the positioning of twinning pipes.
[Fig. 9.2.2]
<A> Install the piping so that oil will not accumulate in the stopped outdoor unit.
unit 1
1.
C
F
The NG example shows that oil accumulates because the units are installed on a reverse gradient while unit 1 is in operation, and unit 3 is stopped.
unit 1
2.
unit 1
h1
h1 = 0.2 m max
The NG example shows that oil accumulates into units 1 and 2 while unit 3 is in operation, and units 1 and 2 are stopped. Vertical pipe height (h1) should be 0.2 m or below.
unit 1
3.
h2
h2 = 0.1 m max
The NG example shows that oil accumulates into unit 1 while unit 3 is in operation, and unit 1 is stopped. Difference between unit and unit in height (h2) should be 0.1 m or below.
unit 1
4.
h2 = 0.1 m max
The NG example shows that oil accumulates into unit 3 while unit 1 is in operation, and unit 3 is stopped. Difference between unit and unit in height (h2) should be 0.1 m or below.
<B> When the piping on the outdoor unit side (from the twinning pipe) exceeds 2 m, ensure a trap (gas pipe only) within 2 m.
Make sure the height of the trap is 200 mm or more.
If there is no trap, oil can accumulate inside the pipe, causing a shortage of oil and may damage the compressor.
F
2 m
Caution:
• Do not install traps other than the ones between outdoor units described on a separate sheet to prevent oil backflow and compressor start-up failure.
• Do not install solenoid valves to prevent oil backflow and compressor start-up failure.
• Do not install a sight glass because it may show improper refrigerant flow.
If a sight glass is installed, inexperienced technicians that use the glass may overcharge the refrigerant.
unit 2
unit 3
A
F
unit 2
unit 3
unit 2
unit 3
unit 2
unit 3
unit 2
unit 3
h2
C
unit 1
unit 2
C
F
F
unit 1
unit 2
h1
h1 > 0.2 m
unit 2
unit 1
h2
h2 > 0.1 m
unit 1
unit 2
h2
h2 > 0.1 m
D
F
E
unit 3
B
unit 3
unit 3
unit 3
C
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pucy-p-ykaPucy-p-yka-bs

Table of Contents