Honeywell Viewguard PIR AM FAI Mounting And Connection Instructions page 15

With anti-mask function; vds class c; vds class b

Advertisement

Available languages

Available languages

Mounting and Connection Instructions Viewguard PIR / AM FAI
9.5
Connection diagram
9.5.1 General functions
FAI logic:
The FAI connections of all detectors are connected to one another. A connection to the control
panel is not required. The LED flashes on the detector that triggers first, the LED light on the
subsequently triggered detectors is static (see 9.4.1).
Contacts:
Alarm
Contact open in the event of an alarm
Fault
Contact open in the event of a fault
Tamper
Contact open in the event of tamper
Backtamper and tamper are both switched to the tamper output.
To comply with VdS and EN 50131-2-2, connect this output to a tamper detector group at the control panel.
9.5.2 Operating mode "Viewguard"
DIP switch setting see table in Chapter 9.1
Fault Tamper Alarm T U F - +
IDS
Control panel
+12 V DC
0 V
alarm
detector zone
tamper
detector zone
walk test
disarmed
shield
If the control panel has no fault input, the "Alarm" and "Fault" outputs can be connected
in series.
9.5.3 Operating mode "SCM 3000 compatible" f
DIP switch setting see table in Chapter 9.1
Difference between operating mode "Viewguard":
The input
"Walk test" (T)
has the function "
Fault Tamper Alarm T U F - +
IDS
Control panel
+12 V DC
0 V
alarm
detector zone
tamper
detector zone
clear
disarmed
shield
Apart from that, the connection diagram of the operating mode "Viewguard" is
applicable (see above).
FAI
Detector 1
or operation with MB-control panel series
Clear
". Details see Installation Instructions of the control panel.
FAI
Detector 1
Fault Tamper Alarm T U F - +
up to max. detector 20
Fault Tamper Alarm
Function of inputs:
(Pull-up resistors in the detector)
Function
armed
armed
disarmed not cleared
disarmed cleared, walk test
The Walk test function remains "on" until next arming.
Detector 2
Detector 3
FAI
FAI
FAI
Function of inputs:
(Pull-up resistors in the detector)
Inputs
Function
walk test disarmed
armed
High
armed
Low
High
disarmed
walk test
Low
Clear alarm memory: Activate and
deactivate walk test.
Alarm end of line resistor
Tamper end of line resistor
End of line resistors in the last
detector. The value depends
on the control panel.
Inputs
clear
High
Low
High
Low (pulse)
15
Detector 20
FAI
High
High
Low
Low
disarmed
High
High
Low
Low