Honeywell T775A Series Installation Instructions Manual page 9

Electronic stand-alone controllers
Hide thumbs Also See for T775A Series:
Table of Contents

Advertisement

.
HONEYWELL MODUTROL MOTOR WITH
VOLTAGE CONTROL INPUT
T1 T2
C R
F
1
POWER
B
R
+
W
MODULATING OUTPUT
B
TERMINAL (MOD 1)
R
+
W
1
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
Fig. 18. Wiring for Mod Motor or Direct Coupled
Actuator with 0 to 10 Vdc Control Input
HONEYWELL ELECTRONIC
SERIES 90 MODUTROL MOTOR
1
T1 T2
B
R
W
POWER
2
B
R
W
+
B
MODULATING
OUTPUT
R
TERMINAL
+
W
(MOD 1)
1
TO VERIFY OUTPUT, TEST OPEN CIRCUIT VOLTAGE BETWEEN
THE MOD 1 TERMINALS W AND R.
- MINIMUM (DRIVE CLOSED) SIGNAL LESS THAN 0.17 VDC
- MAXIMUM (DRIVE OPEN) SIGNAL IS GREATER THAN 1.7 VDC
2
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
3
Fig. 19. Wiring for Series 90 Modutrol Motor Control
All manuals and user guides at all-guides.com
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
.
MODULATING OUTPUT
TERMINAL (MOD 1)
M24483A
3
M24484A
9
HONEYWELL
MINIMUM POSITION
ELECTRONIC SERIES 90
POTENTIOMETER
MODUTROL MOTOR
(Q209)
W R B
T1 T2 B
R
W
1
POWER
B
R
+
W
B
R
+
W
1
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
A 250 OHM RESISTOR PROVIDES 40% AUTHORITY WHEN
2
USING A 150 OHM MINIMUM POSITION POTENTIOMETER.
3
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
Fig. 20. Wiring for Changeover Relay and
Minimum Position Potentiometer Used
with Series 90 Modutrol Motors.
SPDT CHANGEOVER
(H205 OR H705)
2
3
M24485A
62-0254—13