SETUP
OUTPUTS
OPTIONS
USE SCHED
Fig. 58. Setup - Outputs - Options - Schedule.
SETUP
SETUP
OUTPUTS
OUTPUTS
OPTIONS
OPTIONS
MIN OFF
MIN OFF
OR
MIN ON
ENTER
MINIMUM
OFF TIME
FOR RELAYS
Fig. 59. Setup - Outputs - Options - Min Off/On Time.
All manuals and user guides at all-guides.com
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
2.3.3.1. USE SCHED
SETUP
OUTPUTS
OPTIONS
USE SCHED
YES
NO
USE
Selecting NO disables scheduling for all outputs.
SCHEDULE
FOR
Selecting YES enables scheduling for all outputs. When
OUTPUTS
M24521
YES is selected, all individual outputs default to follow the
schedule. However, each individual output can be
removed from scheduling as desired.
With Scheduling enabled, when you return to Program
mode, the new option for Scheduling displays. You can
press the home key and then the menu key to view the
Schedule options in the menu.
See "2.3.1.5. SCHEDULE" on page 23.
2.3.3.2. MIN OFF or MIN ON
SETUP
OUTPUTS
OPTIONS
This is the minimum number of seconds of "off time" or
MIN ON
"on time" for all relays.
0
0
SEC
SEC
ENTER
MINIMUM
ON TIME
FOR RELAYS
M24522A
NOTES:
25
1. Press the
button to display the schedule
selections.
2. Use the
and
buttons to highlight YES or NO.
Default: NO
3. Press the
button to accept the value and display
the MIN OFF option.
1. Press the
button to display the Min Off/On value.
2. Use the
and
buttons to increase/decrease
the desired number of seconds from 0 to 990 sec-
onds in 10 second increments.
Default: 0 (zero)
Range: 0 to 990 seconds
3. Press the
button to accept the seconds and
display the DI OPTIONS.
The minimum OFF or ON time applies to all
1.
relay outputs.
2.
When minimum OFF or ON time is active,
relays waiting to be energized display a
flashing square underneath the relay number
on the home screen.
3.
If the minimum OFF time is not equal to zero
(0), the minimum OFF time activates at
power-up. To manually override, press the
button at any time.