ON-OFF output functions are indicated in the following table:
0:No output
1:Running.ON:Run command is ON or voltage is being output.
2:Run forward.ON: During forward run.
3:Run reverse.ON: During reverse run.
4:Fault output.ON: Inverter is in fault status.
5:FDT1 reached.Please refer to description of F8.16,F8.17.
6:Frequency reached.Please refer to description of F8.20.
7:Zero speed running.ON: The running frequency of inverter and setting frequency
are zero.
8:Preset count value reached.Please refer to description of F8.22.
9:Specified count value reached.Please refer to description of F8.21.
10:overload pre-alarm.When the output current value detection reaches the setting of
Fb.11 and the running time is more than the setting of Fb.12,inverter will output ON
signal.
11:Simple PLC step completed.After simple PLC completes one step,inverter will
output ON signal for 500ms.
12:PLC cycle completed.After simple PLC completes one cycle,inverter will output
ON signal for 500ms.
13:Running time reached.ON:The accumulated running time of inverter is more than
the setting time.