Honeywell
10.4.6 N° burst
Operations: Read/Write
Meaning:
It's a value in point (0 – 255, 0 – FF Hex).
In burst firing mode it rapresents the number of cycles at 50% power demand
10.4.7 Delay time HB
Operations: Read/Write
Meaning:
It's a value in point (0 – 255, 0 – FF Hex).
Each step is 50msec.
It represent a delay to have HB alarm active
When is used soft start this time must be longer than soft start time.
Par126H x 50msec > Par125H x 5msec
When zero crossing firing is used must be less than cycle time
Par126H x 50msec > Par127H x 50msec
10.4.8 Max power for SSR Input
Operations: Read/Write
Meaning:
It's a value in points (0 – 255, 0 – FF Hex).
When SSR input is used it represent the value of the power (%) when is in ON status.
It's the power % when firing command is given on RS485 (1).
Example:
0%
= 0
50%
= 128
100%
= 255
www.honeywell.com/imc
CD3000M-1PH up to 110A
0 (Hex)
80 (Hex)
FF (Hex)
48
User's Manual
Parameter 126L
Parameter 126H
Parameter 127L