10.3.5 Output Power
Command from controller
Operations: Read
Meaning:
It rapresent a value in points (0-255, 0-FF Hex) and it's the power demand in % of controller.
Example:
0%
= 0
50%
= 128
100%
= 255
Command via RS485
Operations : Read/Write
Meaning:
It's a value in points (0-255, 0-FF Hex)
It's power set point setted in thirst buffer
Example:
0%
= 0
50%
= 128
100%
= 255
10.3.6 Power adjust
Operations: Read/Write
Meaning:
Its' a value in points (0-255, 0-FF Hex)
Its' a scaling factor of power demand
Example 1:
0%
= 0
50%
= 128
100% = 255
Example 2:
Output Power :100
Power Limit :100
-> Power real : 100
Output Power :100
Power Limit :50
-> Power real : 50
Output Power :80
Power Limit :50
-> Power real : 40
CD3000M-1PH up to 110A
0 (Hex)
80 (Hex)
FF (Hex)
0 (Hex)
80 (Hex)
FF (Hex)
OUT %
100
80
60
40
20
0
20
40
60
80
43
Honeywell
Parameter 5
Parameter 6
Power Adjust = 100%
Power Adjust = 80%
Power Adjust = 40%
100
Input %
www.honeywell.com/imc