User's Manual
6.2 Auxiliary supply
Warning: this procedure can be done just by specialized personnel.
To change auxiliary supply voltage sold the correct link-jumper on main PCB
Main PCB
If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage
•
(to the load ), use an external transformer.
If load voltage is not included in range of 230V ±15% or 460V +15% provide an external
•
transformer with primary equal to load voltage and secondary 230V if your unit is setted to
230V.
CD3000M-1PH up to 110A
J9
J10
J11
19
230V Auxiliary supply
J9
J11
460V Auxiliary supply
J9
J11
Honeywell
J10
J10
www.honeywell.com/imc