6.2 Auxiliary supply

Warning: this procedure can be done just by specialized personnel.
To change auxiliary supply voltage sold the correct link-jumper on main PCB
Main PCB
If the Auxiliary Voltage (written on the identification label) is different from Supply Voltage
(to the load ), use an external transformer.
If load voltage is not included in range of 230V ±15% or 460V +15% provide an external
transformer with primary equal to load voltage and secondary 230V if your unit is setted to
230V.
CD3000M-1PH up to 110A
J9
J10
J11
19
230V Auxiliary supply
J9
J11
460V Auxiliary supply
J9
J11
Honeywell
J10
J10
www.honeywell.com/imc