Download Print this page
Honeywell GENT S-Quad S4-720 Data And Installation

Honeywell GENT S-Quad S4-720 Data And Installation

Sensor, sounder, speech & strobe
Hide thumbs Also See for GENT S-Quad S4-720:

Advertisement

Quick Links

Data and Installation
S-Quad
Sensor, Sounder, Speech & Strobe
These instructions contain information on the S-Quad product
range. The S-Quad product integrates dual angle smoke, heat
and carbon monoxide gas detection with electronic sounder,
speech and LED flasher (Strobe) in one assembly.
Product range
All LPCB approved Sensor STATES are
listed in the S-Quad Description and
commissioning information .
Part number
Description
S4-720
Heat Sensor
S4-780
Heat Sensor &
Sounder
S4-720-ST-VO Heat Sensor, Speech
& Strobe
S4-715 #
Optical Sensor #
S4-710
Optical & Heat Sensor OH
S4-770
Optical & Heat Sensor
plus Sounder
S4-770-ST
Optical & Heat Sensor
plus Strobe
S4-711
Dual Optical & Heat
Sensor
S4-771
Dual Optical & Heat
Sensor plus Sounder
S4-711-ST
Dual Optical & Heat
Sensor plus Strobe
S4-711-VO
Dual Optical & Heat
Sensor plus Speech
S4-711-ST-VO Dual Optical & Heat
Sensor plus Speech &
Strobe
S4-911
Dual Optical, Heat &
CO Sensor
S4-911-ST-VO Dual Optical, Heat &
CO Sensor plus
Speech & Strobe
# This 'Optical' Sensor is for use in Vigilon Compact system.
4188-779 issue 8-7_08/10_S-Quad _Part 1
www.acornfiresecurity.com
Symbol
H
HS
HStSp
O #
OHS
OHSt
2
O
H
2
O
HS
2
O
HSt
2
O
HSp
2
O
HSpSt
2
O
HCO
2
O
HCOSpSt
www.acornfiresecurity.com
Associated products
S4-700
S4-FLUSH
S4-COVER-DUST
S4-COVER-BASE
S4-EXTRACTOR
S4-COVER-REMOVER Dust cover remover tool
S4-BASE-LABEL
S4-BASE-GASKET
General specification
Operating voltage
35V - 41V
Weight
110g (with base - 170g)
S4-720 only:88g (with base -
148g)
Dimensions
117mm diameter by 49.6mm
height (With base the height
increases to 63.8mm)
IP rating
IP30
IP20 when mounted on a metal
back box
Enclosure
ABS
Colour
RAL 9010
Approval
LPCB approved
Storage Temperature
-20°C to 70°C (for S-Quad
with CO -20°C to 50°C)
Ambient operating
-10°C to 50°C
temperature
Relative Humidity
95% non condensing
(5°C to 45°C)
Heat (H) Standard
EN54 : Part 5 : 2002
Optical (O) Standard
EN54 : Part 7 : 2000
2
EN54 : Part 7 : 2000
Dual Optical (O
)
Standard
Sounder (S) Standard EN54 : Part 3 :
Gas (CO) Standard *
LPS 1274
Multi sensor standard CEA 4021
EN54-18 : 2005
EN54-17 : 2005
V
max
(section 4.8)
V
nom
data:
V
min
V
SO max
V
SO min
* The 'Gas' sensing is designed to meet the requirements
of LPS 1274 : issue 1.0
Information on minimum sound output levels to include polar
dispersion is covered in a technical note TECH7018.033,
available on request from manufacturer.
by Honeywell
S-Quad Base
Semi-Flush fixing kit
Sensor dust cover (50 pack)
Base dust cover (50 pack)
Removal tool
(spare adaptor)
Label plate (50 pack)
Base IP Gasket (50 pack)
42V
I
0.4A
C max
40V
I
1A
S max
24V
I
20mA
L max
16V
Z
0.1W
C max
8V
1

Advertisement

loading

Summary of Contents for Honeywell GENT S-Quad S4-720

  • Page 1 Data and Installation S-Quad by Honeywell Sensor, Sounder, Speech & Strobe Associated products S4-700 S-Quad Base S4-FLUSH Semi-Flush fixing kit S4-COVER-DUST Sensor dust cover (50 pack) S4-COVER-BASE Base dust cover (50 pack) S4-EXTRACTOR Removal tool S4-COVER-REMOVER Dust cover remover tool...
  • Page 2 www.acornfiresecurity.com Data and Installation S-Quad In - Out wiring to S-Quad bases Siting A S-Quad device plugs into a dedicated Base that is installed in the protected premises. The Bases should be sited in locations as defined by the project plans and by BS5839 : Part 1 : 2002. OUT5 OUT5 Do's and Don't...
  • Page 3 www.acornfiresecurity.com S-Quad Data and Installation To fit the dust cover using tool Tools Place the dust cover onto the tool inside the cradle. Offer the cover to the S-Quad, locate and push to fit it onto the assembly. An extractor tool allows removal and fitting of the S-Quad device Withdraw the tool when the dust cover is in place.
  • Page 4 S4-911-ST-VO 0832-CPD-0512 accordance with national or local legislation. Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes.