Optional Module Installation
The following steps must be followed when installing the 4XTMF module:
1.
Remove all power (Primary and Secondary) from the FACP before installing 4XTMF.
2.
Carefully plug the connectors on the 4XTMF module into connectors J12 and J13 on the ES-50X main circuit board, being careful not
to bend any pins.
3.
Secure 4XTMF module to standoffs with supplied screws.
4.
Slide SW2 on the ES-50X main circuit board to the down position.
5.
Enable 4XTMF supervision in user programming. Refer to "4XTMF Supervision" on page 78.
6.
Reapply power to the FACP.
7.
For proper 4XTMF operation, the output relays must be programmed for the factory default settings: Alarm Relay 1, Trouble Relay 2
and Supervisory Relay 3.
8.
When the installation has been complete, enable the 4XTMF module by sliding the disconnect switch to the left.
9.
Test system for proper operation.
ES-50X Series Manual — P/N LS10129-000FL-E:D 4/26/2021
Note: The 4XTMF Module is not directly suitable for transmitting a reverse polarity
supervisory signal. For applications using reverse polarity of a supervisory signal, refer to
Keltron Wiring document #52776.
+
-
+
-
+
-
1
2
3 4
5 6
7
TBL Jumper
Figure 2.15 4XTMF Transmitter Module
}
Remote Alarm (power-limited)*
}
Remote Trouble (power-limited)*
No connection
}
Municipal Box (nonpower-limited)*
Polarities are shown for module activation
Connect to FACP J12 & J13
* Wiring from these
terminals can exit the
protected premises.
Dummy load
terminals 6 and 7
(4.7kΩ, ¼ watt
resistor) if Municipal
Box is not connected.
Disconnect LED
Disconnect Switch
shown in
disconnect position
Installation