Stand-alone operation

In the stand-alone mode the transponder operates with no need of any further connections to
a fire alarm system. To connect local arm devices the relay common fire (Sa-Feu) and/or
common fault (Sa-Stör) may be used.
A fault message may be transmitted via the common fault relay to, e.g. a supervising system
or an authorized person.
Reset
To reset the transponder connect an external reset button (refer to
this case a voltage of 9 to 30 V DC must be switched for at least 1 second at the input (input +/-)
of the IQ8Wireless transponder.
Common fire
Sa-Feuer
IN OUT
-
-
+
+
Fig. 21: Required wiring for the stand–alone operation
Connection data
External power supply 9 V DC to 30 V DC
Jumper J1 and J2 removed
Reset time = 0.2 to 3 seconds
36
Common fault
Sa-Stör
C
NC
NO
R
P
J2
J1
C
Eing
+
NO
NC
Reset
1
) or a relay contact. In
Jumper J1 + J2
removed
U
B
-
-
+
-
9 V DC - 30 V DC
+