Connection Of Two Detector Zones For Individual Fire And Fault Alarm - Honeywell ESSER IQ8 Operation And Installation Instruction

Wireless transponder for wall mounting
Table of Contents

Advertisement

Available languages

Available languages

10.3.1

Connection of two detector zones for individual fire and fault alarm

The application provides the separate transmission of a fault alarm (e.g. battery low message)
and an additional fire alarm message. The fault message is non-latching and is resetted
automatically after the cause of the fault alarm is not present anymore.
Reset
The IQ8Wireless transponder is reset to the functional, normal status when the voltage of the
detector zone "Fire" drops below 5V for at least 60ms (e.g. by switching the fire zone on/off).
The detector zone can also be reset via an external reset button (refer to
In this case a voltage of 9 to 30 V DC must be switched for at least 1 second at the input
(input +/-) of the IQ8Wireless transponder.
FACP
-
Detector zone
+
"Fire"
-
Detector zone
+
"Fault"
1
Reset
Fig. 20: Wiring of two individual detector zones for fire alarm and fault (Example)
Connection data
External power supply 9 V DC to 30 V DC
Detector zone voltage 9 V DC to 30 V DC
R1 quiescent resistor (e.g. 10KΩ for conventional detector zones System 8000/IQ8Control)
R2 alarm resistor (e.g. 1KΩ for conventional detector zones System 8000/IQ8Control)
R3 fault resistor (e.g. 10KΩ for conventional detector zones System 8000/IQ8Control)
Jumpers J1 and J2 inserted (supplied with package)
Reset time = 0.2 to 3 seconds
FB 798941 / 10.06
IQ8Wireless transponder for wall mounting
Common fire
Common fault
Sa-Feuer
Sa-Stör
C
NC
NO
R
P
NO
R1
R2
J2
J1
C
Eing
-
+
+
NC
R3
) or a relay contact.
Jumper J1 + J2
inserted
U
B
-
-
9 V - 30 V DC
+
35