Honeywell Silent Knight IDP-Monitor-2 Installation And Maintenance Instructions
Honeywell Silent Knight IDP-Monitor-2 Installation And Maintenance Instructions

Honeywell Silent Knight IDP-Monitor-2 Installation And Maintenance Instructions

Dual monitor module

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE
INSTRUCTIONS
IDP-Monitor-2
Dual Monitor Module
Specifications
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw:
Average Operating Current: 750µA (LED flashing)
EOL Resistance:
Max. IDC wiring resistance: 1,500 Ohms
Temperature Range:
Humidity:
Dimensions:
Accessories:
Before Installing
This information is included as a quick reference instal-
lation guide. Refer to the control panel installation man-
ual for detailed system information. If the modules will
be installed in an existing operational system, inform the
operator and local authority that the system will be tem-
porarily out of service. Disconnect power to the control
panel before installing the modules.
NOTICE: This manual should be left with the owner/
user of this equipment.
General Description
The Dual Monitor Module is intended for use in intel-
ligent, two wire systems. It provides two independent
2-wire initiating device circuits (IDC), at two separate,
consecutive addresses. It is capable of monitoring nor-
mally open contact fire alarm and supervisory devices, or
either normally open or normally closed security devices.
The module has a single panel controlled red LED.
Compatibility Requirements
To ensure proper operation, this module shall be con-
nected to a compatible Silent Knight system control panel
(list available from Silent Knight).
K200-13-00
5.7 mA (LED on)
47K Ohms
32˚F to 120˚F (0˚C to 49˚C)
10% to 93% Non-condensing
1
1
4
/
˝ H x 4˝ W x 1
/
˝ D
2
4
(Mounts to a 4˝ square by
2
1
/
˝ deep box.)
8
SMB500 Electrical Box
Mounting
Mounts directly to 4˝ square electrical boxes (see Figure
2A). The box must have a minimum depth of 21/8˝.
Surface mounted electrical boxes (SMB500) are available
from Silent Knight.
Wiring
NOTE: All wiring must conform to applicable local
codes, ordinances, and regulations. This module is in-
tended for power limited wiring only.
1. Install module wiring in accordance with the job draw-
ings and appropriate wiring diagrams.
2. Set the address on the module per job drawings.
Note: Monitor module L (using terminals 6 and 7) re-
sponds at the address set on the code switches. Monitor
module H (using terminals 8 and 9) will automatically
respond at the next higher address. For example, if the
code switches are set to 76, module L will respond at
address 76 and module H will respond at address 77.
Use caution to avoid duplicate addressing of modules
on the system.
3. Secure module to electrical box (supplied by installer),
as shown in Figure 2A.
Figure 1. Controls and Indicators:
Figure 2A.
Module mounting:
C0156-00
1
9
0
7 8
6
9
5
8
4
1
3
2
7
2
1 0
TENS
6 7 8 9
5
6
3
4
3
5
4
2
1
0
ONES
ADDRESS
LOOP
C0218-01
Figure 2B:
C0157-00
I56-2730-002

Advertisement

loading

Summary of Contents for Honeywell Silent Knight IDP-Monitor-2

  • Page 1 Mounting Mounts directly to 4˝ square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8˝. Surface mounted electrical boxes (SMB500) are available from Silent Knight. Wiring NOTE: All wiring must conform to applicable local INSTALLATION AND MAINTENANCE codes, ordinances, and regulations.